Please upgrade your browser. This site requires a newer version to work correctly. Read more
Our "watch" feature allows you to stay current on all aspects of this specific credit. In your account, you can control what you get updated on and how you receive your notifications. Hide

| v4 - LEED v4

Indoor water use reduction

Required

Intent

To reduce indoor water consumption.

Requirements

Building Water Use

For the fixtures and fittings listed in Table 1, as applicable to the project scope, reduce aggregate water consumption by 20% from the baseline. Base calculations on the volumes and flow rates shown in Table 1.

All newly installed toilets, urinals, private lavatory faucets, and showerheads that are eligible for labeling must be WaterSense labeled (or a local equivalent for projects outside the U.S.).

Projects where fixtures or fixture fittings are not within the tenant spaces are exempt from this prerequisite.

Table 1. Baseline water consumption of fixtures and fittings

Commercial Fixtures, Fittings, and Appliances Current Baseline (IP Units) Current Baseline (SI units)
Water closets (toilets)* 1.6 gallons per flush (gpf) 6 liters per flush (lpf)
Urinal* 1.0 (gpf) 3.8 lpf
Public lavatory (restroom) faucet 0.5 gpm at 60 psi all others except private applications 1.9 lpm at 415 kPa, all others except private applications
Private lavatory faucet* 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
Kitchen faucet (excluding faucets used exclusively for filling operations) 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
Showerhead* 2.5 gpm at 80 psi per shower stall 9.5 lpm at 550 kPa per shower stall
* WaterSense label available for this product type
gpf = gallons per flush
gpm = gallons per minute
psi = pounds per square inch
lpf = liters per flush
lpm = liters per minute
kPa = kilopascals

Appliance and process water use

Install appliances, equipment, and processes within the project scope that meet the requirements listed in the tables below .

Table 2. Standards for appliances

Appliance Requirement
Residential clothes washers ENERGY STAR or performance equivalent
Commercial clothes washers CEE Tier 3A
Residential dishwashers (standard and compact) ENERGY STAR or performance equivalent
Prerinse spray valves ≤ 1.3 gpm (4.9 lpm)
Ice machine ENERGY STAR or performance equivalent and use either air-cooled or closed-loop cooling, such as chilled or condenser water system

gpm = gallons per minute
lpm = liters per minute

Table 3. Standards for processes

Process Requirement
Heat rejection and cooling No once-through cooling with potable water for any equipment or appliances that reject heat
Cooling towers and evaporative condensers Equip with:
  • makeup water meters
  • conductivity controllers and overflow alarms
  • efficient drift eliminators that reduce drift to maximum of 0.002% of recirculated water volume for counterflow towers and 0.005% of recirculated water flow for cross-flow towers

Join LEEDuser

Ask questions, share tips, and get notified of new forum posts by joining LEEDuser, a tool developed by BuildingGreen and supported by USGBC!

  • Share on Twitter
  • Share on Facebook
  • Share on LinkedIn
  • Print to PDF
Sample forms
Version: v01
Active Form
Version: v02
Active Form
View all sample forms

0 commentsLeave a comment

Leave a comment Don't have an account? Create one

You must be signed in to leave a comment.