| v2 - LEED 2.0

Toxic material source reduction - reduced mercury in light bulbs

MRp2 | Required

Intent

Establish and maintain a toxic material source reduction program to reduce the amount of mercury brought into buildings through purchases of light bulbs.

Requirements

  • Maintain mercury content of all mercury-containing light bulbs below 100 picograms per lumen hour, on weighted average, for all mercury-containing light bulbs acquired for the existing building and associated grounds.
  • The weighted average mercury content of these mercury-containing light bulbs is calculated by: 1) adding up the total weight of mercury in all the mercury-containing light bulbs acquired during the performance period (picograms of Hg); and then, 2) dividing total mercury content (picograms of Hg) by the sum of the lumen hour output of all the light bulbs (lumen hours: calculated by multiplying the rated hours (life) of each light bulb by the mean light output in lumens).
    • Rated hours of life are defined as stated by the manufacturer based on consistent testing (three hours on/20 minutes off for linear fluorescents and compact fluorescents; 11 hours on for HID light bulbs) and are based on the design or mean light output of the light bulbs (in lumens, fluorescent light bulbs measured with a ballast having a ballast factor of 1.0 and measured using instant-start ballasts except for T-5s, which are measured using program start ballasts).
    • The mean light output in lumens is the light output at 40% of light bulb life.
    • These calculations need to show for all acquired mercury containing light bulbs:
      • The total mercury content in the light bulbs.
      • The total lumen hours of light output for all the light bulbs.
      • The number of light bulbs of each type.
      • The overall weighted average mercury content in picograms/lumen hour.
    • If the mercury content documentation shows a range of mercury contents in milligrams, use the highest value in the range in these calculations.
Join LEEDuser

Ask questions, share tips, and get notified of new forum posts by joining LEEDuser, a tool developed by BuildingGreen and supported by USGBC!

  • Share on Twitter
  • Share on Facebook
  • Share on LinkedIn
  • Print to PDF
Sample forms
View sample forms

0 commentsLeave a comment

Leave a comment Don't have an account? Create one

You must be signed in to leave a comment.