| v3 - LEED 2009

Daylight and views - views

EQc8.2 | Possible 3 points

Intent

To provide building occupants a connection to the outdoors through the introduction of daylight and views into the regularly occupied areas of the building.

Requirements

Provide access to views that meet the following criteria below.

INPATIENT UNITS (1 point)

A minimum of 90% of the inpatient units, staff areas, and public areas shall be within 20 feet—or twice the window head height, whichever is smaller—of the perimeter. All such perimeter areas must have windows that provide at least an 11° angle of unobstructed view in the vertical and horizontal direction.

NON-INPATIENT AREAS (1-2 points)

In the block planning stage, configure the building floor plates such that the area within 15 feet of the perimeter exceeds the perimeter area requirement as determined by the table outlined below.

Confirm at the conclusion of detailed planning that 90% of the perimeter rooms have windows that provide at least an 11° angle of unobstructed view in the vertical and horizontal direction.

Perimeter Non-IPU Area with Window Access Required      
Floor plate area (bgsf) Threshold A:
1 point
Threshold B:
2 points
Floor plate area (bgm2) Threshold A:
1 point
Threshold B:
2 points
Up to 15,000 7348 8248 Up to 1,395 683 766
20,000 8785 9985 1,800 816 928
25,000 10087 11587 2,325 937 1076
30,000 11292 13092 2,785 1,049 1,216
35,000 12425 14525 3,250 1,154 1,350
40,000 13500 15900 3,715 1,254 1,477
45,000 14528 17228 4,180 1,350 1,601
50,000 and larger 15516 18516 4,600 and larger 1,441 1,720

For both in-patient and non-inpatient areas, portions of side lit areas beyond the 15’ view area boundary that meet the requirements of IEQ Credit 8.1: Daylight and Views—Daylight may be included in the qualifying areas of this credit.

For calculation methodology for floor plates that vary in size and configuration, see the LEED Reference Guide for Green Building Design & Construction, 2009 Edition Healthcare Supplement.

Join LEEDuser

Ask questions, share tips, and get notified of new forum posts by joining LEEDuser, a tool developed by BuildingGreen and supported by USGBC!

  • Share on Twitter
  • Share on Facebook
  • Share on LinkedIn
  • Print to PDF
Sample forms
Version: v04
Active Form Static Form
View all sample forms

0 commentsLeave a comment

Leave a comment Don't have an account? Create one

You must be signed in to leave a comment.