PBT source reduction - mercury

MRp2 | Required

Intent

To reduce mercury-containing products and devices and mercury discharge through product substitution, capture and recycling.

Requirements

  • ƒ As part of the recycling collection system developed in compliance with MR Prerequisite 1:
    Storage and Collection of Recyclables, identify:

    • types of mercury containing products and devices1 to be collected,

    • criteria governing how they are to be handled by a recycling program, and
    • disposal methods for captured mercury.
  • In facilities delivering dental care, specify and install amalgam separation devices that meet or exceed the standard ISO-11143.
  • Comply with the mercury elimination requirement outlined in the 2010 FGI Guidelines for Design and Construction of Health Care Facilities (Section A1.3- 4b: Mercury Elimination).
    • 4.2.1.1 New construction. In new construction, healthcare facilities shall not use mercury-containing equipment, including thermostats, switching devices, and other building system sources. (Lamps are excluded.)

    • 4.2.1.2 Renovation. For renovation, healthcare facilities shall develop a plan to phase out mercury-containing products and upgrade current mercury-containing lamps to high efficiency, low mercury or mercury free lamp technology.
  • ƒƒDo not specify or install preheat, T-9, T-10, or T-12 fluorescents or mercury vapor type high intensity discharge (HID) lamps in the project. Do not specify probe start metal halide HID lamps in interior spaces in the project.
    ƒƒ
  • Only specify and install illuminated exit signs that use Light-Emitting Diode (LED) or Light-Emitting Capacitor (LEC) lamps and use less than 5 watts of electricity.
    ƒƒ
  • Specify and install fluorescent and high-pressure sodium lamps that meet the following criteria:

1Applicable mercury-containing products and devices include, but are not limited to, lamps (such as linear and circular fluorescents, integrally ballasted and non-integrally ballasted compact fluorescents and HIDs) and dental wastes (such as scrap amalgam, chair side traps, and separator wastes).

Join LEEDuser

Ask questions, share tips, and get notified of new forum posts by joining LEEDuser, a tool developed by BuildingGreen and supported by USGBC!

  • Share on Twitter
  • Share on Facebook
  • Share on LinkedIn
  • Print to PDF
Sample forms
Version: v04
Active Form Static Form
View all sample forms

0 commentsLeave a comment

Leave a comment Don't have an account? Create one

You must be signed in to leave a comment.