System Downtime Notification
From Saturday, August 30, 2014 from 8:00 am EST to 11:59 pm EST, usgbc.org will be offline for site maintenance.
Email us or call 1-800-795-1747 for assistance. Thanks for your patience.
Please upgrade your browser. This site requires a newer version to work correctly. Read more
Our "watch" feature allows you to stay current on all aspects of this specific credit. In your account, you can control what you get updated on and how you receive your notifications. Hide

| v3 - LEED 2009

Water use reduction - building equipment

WEc4.1 | Possible 1 point

Intent

To reduce or eliminate the use of potable water for non-potable process use in building system equipment.

Requirements

  • Install only dry vacuum pumps for central vacuum systems and all other systems except for vacuum systems for sterilizing, which may use oil-lubricated liquid ring pumps.
  • Do not install venturi vacuum systems for sterilizers. For air compressors, install either air cooling or closed-loop cooling, such as a cooling tower or chilled water system.
  • Large frame X-ray processors and/or developers of more than 150 mm (six inches) in length or width shall use film processor water recycling units. Smaller X-ray equipment, such as a dental X-ray film processor, is exempt from this requirement

.

Join LEEDuser

Ask questions, share tips, and get notified of new forum posts by joining LEEDuser, a tool developed by BuildingGreen and supported by USGBC!

  • Share on Twitter
  • Share on Facebook
  • Share on LinkedIn
  • Print to PDF
Sample forms
Version: v04
Active Form Static Form
View all sample forms

0 commentsLeave a comment

Leave a comment Don't have an account? Create one

You must be signed in to leave a comment.