Water use reduction - food waste systems

WEc4.3 | Possible 1 point

Intent

To reduce or eliminate the use of potable water for non-potable process use in building system equipment.

Requirements

When a food waste disposer system is used, the following requirements must be met:

  • Use cold water. (This is a common code requirement.)
  • Equip systems with a load sensing device that regulates the water use to 1 gpm in a no- load situation and 3 to 8 gpm in a full-load situation.
  • Automatic time shutoff that shall have a ten-minute time-out system with a push button to reactivate.

When pulpers, extractors, scrap basket or strainer-type systems are used, the following requirements must be met:

  • Mechanical pulpers/extractors and mechanical scrapper systems shall use no more than 2 gpm of potable water, excluding end-of-day, wash-down cycles.
  • Non-mechanical strainer (scrapper) baskets shall not be part of a flowing trough collection system connected to potable water at a rate greater than 2 gpm.
  • Automatic time shutoff that shall have a ten-minute time-out system with a push button to reactivate.
Join LEEDuser

Ask questions, share tips, and get notified of new forum posts by joining LEEDuser, a tool developed by BuildingGreen and supported by USGBC!

  • Share on Twitter
  • Share on Facebook
  • Share on LinkedIn
  • Print to PDF
Sample forms
Version: v04
Active Form Static Form
View all sample forms

0 commentsLeave a comment

Leave a comment Don't have an account? Create one

You must be signed in to leave a comment.