Water heating

EAc7 | Possible 6 points

Intent

Reduce energy consumption associated with the domestic hot water system, including improving the efficiency of both the hot water system design and the layout of the fixtures in the home.

Requirements

Prerequisites

None.

Credits

7.1 Efficient hot water distribution (2 points). Design and install an energy-efficient hot water distribution system (see Figure 1). None of the branch length requirements below apply to cold water demand loads (e.g., toilets), washing machines, or tubs without showerheads. Select one of the following designs:

a. Structured plumbing system. The system must meet all of the following:
i. The system must have a demand-controlled circulation loop that is insulated to at least R-4.
ii. The total length of the circulation loop must be less than 40 linear feet of plumbing in one-story homes. Add 2x the ceiling height for two-story homes, and add 4x the ceiling height for three- or four-story homes.
iii. Branch lines from the loop to each fixture must be ≤10 feet long and a maximum of ½-inch nominal diameter.
iv. The system must be designed with a push button control in each full bathroom and the kitchen and an automatic pump shut-off.

b. Central manifold distribution system. The system must meet all of the following:
i. The central manifold trunk must be no more than 6 feet in length.
ii. The central manifold trunk must be insulated to at least R-4.
iii. No branch line from the central manifold to any fixtures may exceed 20 feet in one-story homes. Add 1x the ceiling height for two-story homes, and add 2x the ceiling height for three- or four-story homes.
iv. Branch lines from the manifold must be a maximum of ½-inch nominal diameter.

c. Compact design of conventional system. The system must meet all of the following:
i. No branch line from the water heater to any fixtures may exceed 20 feet in one-story homes. Add 1x the ceiling height for two-story homes, and add 2x the ceiling height for three- or four-story homes.
ii. Branch lines from the central header to each fixture must be a maximum of ½-inch nominal diameter.

7.2 Pipe insulation (1 point). All domestic hot water piping shall have R-4 insulation. Insulation shall be properly installed on all piping elbows to adequately insulate the 90-degree bend.

7.3 Efficient domestic hot water (DHW) equipment (maximum 3 points). Design and install energy-efficient water heating equipment. Select one measure from Table 1 below.

Table 1 High-Efficiency Water Heating Equipment

Water heater type and efficiency requirement Description  Points
Gas water heaters    
EF ≥ 0.53 (80 gallon) High-efficiency storage water heater 1
EF ≥ 0.57 (60 gallon) High-efficiency storage water heater 1
EF ≥ 0.61 (40 gallon) High-efficiency storage water heater 1
EF ≥ 0.8 Storage or tankless water heater 2
CAE ≥ 0.8 Combination water and space heaters 2
Electric water heaters    
EF ≥ 0.89 (80 gallon) High-efficiency storage water heater 1
EF ≥ 0.92 (50 gallon) High-efficiency storage water heater 1
EF ≥ 0.93 (40 gallon) High-efficiency storage water heater 1
EF ≥ 0.99 Tankless water heater 2
EF ≥ 2.0 Heat pump water heater 3
Solar water heaters (backup)    
≥ 40% of annual DHW load With preheat tank 2
≥ 60% of annual DHW load With preheat tank 3

Join LEEDuser

Ask questions, share tips, and get notified of new forum posts by joining LEEDuser, a tool developed by BuildingGreen and supported by USGBC!

  • Share on Twitter
  • Share on Facebook
  • Share on LinkedIn
  • Print to PDF
Sample forms
View sample forms

0 commentsLeave a comment

Leave a comment Don't have an account? Create one

You must be signed in to leave a comment.