Intent
To maximize the energy performance of windows.
Requirements
Design and install windows, skylights, and glass doors whose ratings from the National Fenestration Rating Council exceed the requirements in the ENERGY STAR for Homes, version 3, prescriptive pathway, as shown in Tables 1–3. Use the average window ratings, average skylight ratings, and average exterior door ratings.
Determine the window-to-floor-area (WFA) ratio by calculating the total window area in the above-grade conditioned floor area. All skylight window areas count toward the WFA ratio. For decorative glass, the project team may exclude up to 0.75% of the WFA ratio from the calculations. If the WFA ratio is 15% or more, the following additional requirements apply:
- In climate zones 4–8, homes with a WFA ratio of 15% or more must meet a more stringent U-factor requirement:
U-factor = (0.15 / WFA) * (U-factor from Table 1)
- In climate zones 1–3, homes with a WFA ratio of 15% or more must meet a more stringent solar heat gain coefficient (SHGC) requirement:
SHGC = (0.15 / WFA) * (SHGC from Table 1)
Project teams that achieve EA Credit Building Orientation for Solar Design are exempt from the requirements for window SHGC.
Table 1. Points for exceeding baseline window ratings
| Climate zone | Points | ||||
|---|---|---|---|---|---|
| 1, 2 | 3 | 4 | 5–8 | ||
| U-factor | ≤ 0.45 | ≤ 0.30 | ≤ 0.26 | ≤ 0.26 | 1.5 |
| SHGC | ≤ 0.25 | ≤ 0.25 | ≤ 0.40 | Any | |
| U-factor | ≤ 0.30 | ≤ 0.26 | ≤ 0.22 | ≤ 0.22 | 3 |
| SHGC | ≤ 0.25 | ≤ 0.25 | ≤ 0.40 | Any | |
SHGC = solar heat gain coefficient
Table 2. Points for exceeding baseline skylight ratings
| Climate zone | Points | ||||
|---|---|---|---|---|---|
| 1, 2 | 3 | 4 | 5–8 | ||
| U-factor | ≤ 0.70 | ≤ 0.57 | ≤ 0.47 | ≤ 0.47 | 1.5 |
| SHGC | ≤ 0.25 | ≤ 0.25 | ≤ 0.40 | Any | |
| U-factor | ≤ 0.47 | ≤ 0.47 | ≤ 0.40 | ≤ 0.40 | 3 |
| SHGC | ≤ 0.25 | ≤ 0.25 | ≤ 0.40 | Any | |
SHGC = solar heat gain coefficient
Table 3. Points for exceeding baseline door ratings
| Opaque | ≤ 1/2 lite | > 1/2 lite | |
|---|---|---|---|
| U-factor | 0.21 | 0.27 | 0.32 |
| SHGC | N/A | 0.30 | 0.30 |
SHGC = solar heat gain coefficient