Environmental Tobacco Smoke (ETS) control

EQp2 | Required

Intent

Prevent exposure of building occupants and systems to Environmental Tobacco Smoke (ETS).

Requirements

Zero exposure of nonsmokers to ETS by prohibition of smoking in the building, OR, provide a designated smoking room designed to effectively contain, capture and remove ETS from the building. At a minimum, the smoking room shall be directly exhausted to the outdoors with no recirculation of ETS-containing air to the nonsmoking area of the building, enclosed with impermeable structural deck-to-deck partitions and operated at a negative pressure compared with the surrounding spaces of at least 7 Pa (0.03 inches of water gauge).

Performance of smoking rooms shall be verified using tracer gas testing methods as described in the ASHRAE Standard 129-1997. Acceptable exposure in nonsmoking areas is defined as less than 1% of the tracer gas concentration in the smoking room detectable in the adjoining nonsmoking areas. Smoking room testing as described in the ASHRAE Standard 129-1997 is required in the contract documents and critical smoking facility systems testing results must be included in the building commissioning plan and report or as a separate document.

Join LEEDuser

Ask questions, share tips, and get notified of new forum posts by joining LEEDuser, a tool developed by BuildingGreen and supported by USGBC!

  • Share on Twitter
  • Share on Facebook
  • Share on LinkedIn
  • Print to PDF
Sample forms
View sample forms

0 commentsLeave a comment

Leave a comment Don't have an account? Create one

You must be signed in to leave a comment.