| v2 - LEED 2.1

Measurement and verification

EAc5 | Possible 1 point

Intent

Provide for the ongoing accountability and optimization of building energy and water consumption performance over time.

Requirements

Install continuous metering equipment for the following end-uses:

  • Lighting systems and controls
  • Constant and variable motor loads
  • Variable frequency drive (VFD) operation
  • Chiller efficiency at variable loads (kW/ton)
  • Cooling load
  • Air and water economizer and heat recovery cycles
  • Air distribution static pressures and ventilation air volumes
  • Boiler efficiencies
  • Building-related process energy systems and equipment
  • Indoor water risers and outdoor irrigation systems

Develop a Measurement and Verification plan that incorporates the monitoring information from the above end-uses and is consistent with Option B, C or D of the 2001 International Performance Measurement & Verification Protocol (IPMVP) Volume I: Concepts and Options for Determining Energy and Water Savings.

Join LEEDuser

Ask questions, share tips, and get notified of new forum posts by joining LEEDuser, a tool developed by BuildingGreen and supported by USGBC!

  • Share on Twitter
  • Share on Facebook
  • Share on LinkedIn
  • Print to PDF
Sample forms
View sample forms

0 commentsLeave a comment

Leave a comment Don't have an account? Create one

You must be signed in to leave a comment.