Indoor water use reduction

WE2 | Possible point

Intent

To reduce indoor water consumption.

To reduce effects on natural water resources and reduce burdens on community water supply and wastewater systems.

To increase water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

To further increase water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

To reduce indoor fixture and fitting water use within buildings to reduce the burdens on potable water supply and wastewater systems.

To maximize indoor plumbing fixture and fitting efficiency within buildings to reduce the use of potable water and consequent burden on municipal water supply and wastewater systems.

To further increase water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

To maximize water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

Maximize water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

Maximize water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

To reduce indoor fixture and fitting water use within buildings to reduce the burdens on potable water supply and wastewater systems.

To maximize indoor plumbing fixture and fitting efficiency within buildings to reduce the use of potable water and consequent burden on municipal water supply and wastewater systems.

Maximize water efficiency within tenant spaces to reduce the burden on municipal water supply and wastewater systems.

Maximize water efficiency within tenant spaces to reduce the burden on municipal water supply and wastewater systems.

To reduce effects on natural water resources and reduce burdens on community water supply and wastewater systems.

Maximize fixture water efficiency within buildings to reduce the burden on potable water supply and wastewater systems.

Maximize fixture potable water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

Maximize water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

Maximize water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

Maximize water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

Maximize water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

Maximize water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

Maximize water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

To reduce indoor water consumption.

Maximize water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

Maximize fixture potable water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

To maximize indoor plumbing fixture and fitting efficiency within buildings to reduce the use of potable water and consequent burden on municipal water supply and wastewater systems.

To maximize indoor plumbing fixture and fitting efficiency within buildings to reduce the use of potable water and consequent burden on municipal water supply and wastewater systems.

To reduce indoor water consumption.

To reduce indoor water consumption.

To reduce indoor water consumption.

To reduce indoor water consumption.

To reduce indoor water consumption.

To reduce indoor water consumption.

To reduce indoor water consumption.

To reduce indoor water consumption.

To reduce indoor water consumption.

To reduce indoor water consumption.

To reduce indoor water consumption.

To reduce indoor water consumption.

To reduce indoor water consumption.

To reduce indoor water consumption.

To reduce indoor water consumption.

To increase water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

To further increase water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

To increase water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

To further increase water efficiency within buildings to reduce the burden on municipal water supply and wastewater systems.

Requirements

Further reduce fixture and fitting water use from the calculated baseline in WE Prerequisite Indoor Water Use Reduction. Additional potable water savings can be earned above the prerequisite level using alternative water sources. Include fixtures and fittings necessary to meet the needs of the occupants. Some of these fittings and fixtures may be outside the tenant space (for Commercial Interiors) or project boundary (for New Construction). Points are awarded according to Table 1.

Table 1. Points for reducing water use

Percentage reduction Points (BD&C) Points (Schools, Retail, Hospitality, Healthcare) Points (ID&C) Points (CI Retail) Points (CI Hospitality)
25% 1 1 2 2 2
30% 2 2 4 4 4
35% 3 3 6 6 6
40% 4 4 8 8 8
45% 5 5 10 10 10
50% 6 -- 12 -- 11

For nonresidential buildings, mixed-use buildings, and multifamily residential buildings four stories or more:

Indoor water usage in new buildings and buildings undergoing major renovations as part of the project must be an average 20% less than in baseline buildings. The baseline usage is based on the requirements of the United States Energy Policy Act of 1992 and subsequent rulings by the Department of Energy, the requirements of the United States Energy Policy Act of 2005, and the fixture performance standards in the 2006 editions of the Uniform Plumbing Code or International Plumbing Code as to fixture performance. Calculations are based on estimated occupant usage and include only the following fixtures and fixture fittings (as applicable to the project scope): water closets (toilets), urinals, lavatory faucets, showers, kitchen sink faucets, and prerinse spray valves.

The water efficiency threshold is calculated as a weighted average of water usage for the buildings constructed as part of the project based on their conditioned area. Projects may also follow the LEED for Multiple Buildings and On-Campus Building Application Guide alternative calculation methodology to show compliance with this prerequisite.

Commercial fixtures, fittings, or appliances Baseline water usage
Commercial toilet 1.6 gpf1  (6 lpf1)
Except blow-out fixtures, 3.5 gpf (13.2 lpf)
Commercial urinal 1.0 gpf (4 lpf)
Commercial lavatory (restroom) faucet 2.2 gpm at 60 psi (8.5 lpm)  at 4 bar ( 58 psi), private applications only (hotel-motel guest rooms, hospital patient rooms)
0.5 gpm at 60 psi2 (2 lpm)  at  4 bar (58 psi) all others except private applications
0.25 gallons per cycle for metering faucets (1 liter per cycle)
Commercial prerinse spray valve (for food service applications) Flow rate ≤ 1.6 gpm (6 lpm) (no pressure specified; no performance requirement)
1 EPAct 1992 standard for toilets applies to both commercial and residential models.
2 In addition to EPAct requirements, the American Society of Mechanical Engineers standard for public lavatory faucets is 0.5 gpm at 60 psi (2 lpm) at  4 bar (58 psi)
(ASME A112.18.1-2005). This maximum has been incorporated into the national Uniform Plumbing Code and the International Plumbing Code.

Residential Fixtures, Fittings, and Appliances Baseline water usage
Residential toilet 1.6 gpf3 (6 lpf3)
Residential lavatory (bathroom) faucet 2.2 gpm at 60 psi (8.5 lpm)  at 4 bar ( 58 psi)
Residential kitchen faucet
Residential showerhead 2.5 gpm at 80 psi per shower stall4 (9.5 lpm) at 5.5 bar (80 psi)
gpf = gallons per flush; psi = pounds per square inch.
Source: Adapted from information developed and summarized by the U.S. EPA Office of Water.
3 EPAct 1992 standard for toilets applies to both commercial and residential models.
4 Residential shower compartment (stall) in dwelling units: The total allowable flow rate from all flowing showerheads at any given time, including rain systems, waterfalls, bodysprays, bodyspas, and jets, shall be limited to the allowable showerhead flow rate as specified above (2.5-gpm or  9.5 lpm ) per shower compartment, where the floor area of the shower compartment is less than 2,500 sq.in. (1,600,000 sq. mm). For each increment of 2,500 sq.in. (1,600,000 sq. mm). of floor area thereafter or part thereof, an additional showerhead with total allowable flow rate from all flowing devices equal to or less than the allowable flow rate as specified above shall be allowed. Exception: Showers that emit recirculated non-potable water originating from within the shower compartment while operating are allowed to exceed the maximum as long as the total potable water flow does not exceed the flow rate as specified above.

The following fixtures, fittings, and appliances are outside the scope of the water use reduction calculation:

  1. Commercial steam cookers.
  2. Commercial dishwashers.
  3. Automatic commercial ice makers.
  4. Commercial (family-sized) clothes washers.
  5. Residential clothes washers.
  6. Standard and compact residential dishwashers.
AND

For new single-family residential buildings and new multiunit residential buildings three stories or fewer, 90% of buildings must use a combination of fixtures that would earn 3 points under LEED for Homes 2008 WE Credit 3, Indoor Water Use.

Employ strategies that in aggregate use 20% less water than the water use baseline calculated for the building (not including irrigation).

Calculate the baseline according to the commercial and/or residential baselines outlined below1. Calculations are based on estimated occupant usage and must include only the following fixtures and fixture fittings (as applicable to the project scope): water closets, urinals, lavatory faucets, showers, kitchen sink faucets and pre-rinse spray valves. [Europe ACP: Water Use Baseline]

Commercial Fixtures, Fittings, and Appliances Current Baseline (Imperial Units) Current Baseline (Metric units)
Commercial Toilets 1.6 gallons per flush (gpf)*
Except blow-out fixtures: 3.5 (gpf)
6 liters per flush (lpf)
Except blow-out fixtures: 13 lpf
Commercial Urinals 1.0 (gpf) 4 lpf
Commercial Lavatory (Restroom) Faucets 2.2 gallons per minute (gpm) at 60 pounds per
square inch (psi), private applications only (hotel
or motel guest rooms, hospital patient rooms)
0.5 (gpm) at 60 (psi)** all others except private
applications
0.25 gallons per cycle for metering faucets
8.5 liters per minute (lpm) at 4 bar (58 psi),
private applications only (hotel or motel guest
rooms, hospital patient rooms)
2.0 lpm at 4 bar (58 psi), all others except
private applications
1 liter per cycle for metering faucets
Showerheads 2.5 (gpm) at 80 (psi) per shower stall **** 9.5 lpm at 5 bar (58 psi)
For projects with commercial pre-rinse spray valves, the flow rate must comply with the asME a112.18.1 standard of 1.6 gpm or less.

Residential fixtures, fittings, and appliances Current baseline (imperial units) Current baseline (metric units)
Residential toilets 1.6 (gpf)*** 6 liters per flush (lpf)
Except blow-out fixtures: 13 lpf
Residential lavatory (bathroom) faucets 2.2 (gpm) at 60 psi 4 lpm
8.5 lpm at 4 bar (58 psi), private applications only
(hotel or motel guest rooms, hospital patient rooms)
2.0 lpm at 4 bar (58 psi), all others except private
applications
1 liter per cycle for metering faucets
Residential kitchen faucet
Residential showerheads 2.5 (gpm) at 80 (psi) per shower stall**** flow rate ≤ 6.1 lpm
(no pressure specified; no performance requirement)
* EPAct1992 standard for toilets applies to both commercial and residential models.
** in addition to Epact requirements, the american society of Mechanical Engineers standard for public lavatory faucets is 0.5 gpm at 60 psi (2.0 lpm at 4 bar (58 psi)) (asME a112.18.1-2005). this maximum has been incorporated into the national uniform plumbing Code and the international plumbing Code.
*** EPAct 1992 standard for toilets applies to both commercial and residential models.
**** residential shower compartment (stall) in dwelling units: the total allowable flow rate from all flowing showerheads at any given time, including rain systems, waterfalls, bodysprays, bodyspas and jets, must be limited to the allowable showerhead flow rate as specified above (2.5 gpm) per shower compartment, where the floor area of the shower compartment is less than 2,500 square inches (1.5 square meters). for each increment of 2,500 square inches (1.5 square meters) of floor area thereafter or part thereof, an additional showerhead with total allowable flow rate from all flowing devices equal to or less than the allowable flow rate as specified above must be allowed. Exception: showers that emit recirculated nonpotable water originating from within the shower compartment while operating are allowed to exceed the maximum as long as the total potable water flow does not exceed the flow rate as specified above.

The following fixtures, fittings and appliances are outside the scope of the water use reduction calculation:

  • Commercial Steam Cookers
  • Commercial Dishwashers
  • Automatic Commercial Ice Makers
  • Commercial (family-sized) Clothes Washers
  • Residential Clothes Washers
  • Standard and Compact Residential Dishwashers

Alternative Compliance Paths (ACPs)

Europe ACP: Water Use Baseline

Projects in Europe may use the values defined by European Standards.

Employ strategies that in aggregate use less water than the water use baseline calculated for the building (not including irrigation). The minimum water savings percentage for each point threshold is as follows:

Building Use Reduction Process Use Reduction Points
30% AND 30% 2
35% AND 35% 3
40% AND 40% 4

Building water use

Calculate the baseline according to the commercial baselines outlined below1. Calculations are based on estimated occupant usage. Include only the following fixtures and fixture fittings (as applicable): water closets, urinals, lavatory faucets, showers, kitchen sink faucets, and pre-rinse spray valves. [Europe ACP: Water Use Baseline]

Fixtures, Fittings, and Appliances Current Baseline (Imperial Units) Current Baseline (Metric Units)
Commercial Toilets 1.6 gallons per flush (gpf)*
Except blow-out fixtures: 3.5 (gpf)
6 liters per flush (lpf)
Except blow-out fixtures: 13.5 lpf
Commercial Urinals 1.0 (gpf) 4.0 lpf
Commercial Lavatory (restroom) Faucets 2.2 gallons per minute (gpm) at 60 pounds per square inch (psi),private applications only (hotel or motel guest rooms, hospital patient rooms)
0.5 (gpm) at 60 (psi)**all others except private applications
0.25 gallons per cycle for metering faucets
8.5 liters per minute (lpm) at 4 bar (58 psi), private applications only (hotel or motel guest rooms, hospital patient rooms)
2.0 lpm at 4 bar (58 psi), all others except private applications
1 liter per cycle for metering faucets
Shower 2.5 (gpm) at 80 (psi) per shower stall 9.5 lpm  at 5.5 bar (80 psi) per shower stall
Kitchen Faucet 2.2 (gpm) at 60 (psi) 8.5 lpm at 4 bar (58 psi)
Commercial Pre-rinse Spray Valves
(for food service applications)
Flow rate ≤ 1.6 (gpm)
(no pressure specified; no performance requirement)
Flow rate ≤ 6 lpm (no pressure specified; no performance requirement)
*    EPAct 1992 standard for toilets applies to both commercial and residential models.
**  In addition to EPAct requirements, the American Society of Mechanical Engineers standard for public lavatory faucets is 0.5 gpm at 60 psi (2.0 lpm at 4 bar (58 psi)) (ASME A112.18.1–2005).
This maximum has been incorporated into the national Uniform Plumbing Code and the International Plumbing Code.

AND

Commercial water use

Employ strategies that in aggregate use less water than the water use baseline calculated for commercial equipment performance requirements as listed in the following table. Base the calculations on estimated occupant usage. Include only the following fixtures (as applicable): clothes washers, dishwashers, ice machines, food steamers, and combination ovens.

Exemptions from calculations:

  • Appliances and equipment that use water for human consumption may be excluded. Examples: bread misters, produce misters, soda machines, coffee-making machines, and fixtures used to fill sinks for washing produce.
  • Equipment, appliances, fixtures, and fittings that are not covered by the Energy Policy Act of 1992 (EPAct 1992), do not contribute toward the retail process, and are not commercially rated may be excluded. Example: a residential dishwasher in an employee break room.
  • Fixtures whose flow rates are regulated by health codes may be excluded. Example: fixtures used for filling dishwashing sinks in which water must be maintained at a certain temperature.

Commercial Equipment Baseline (Imperial Units) Baseline (Metric Units)
Commercial clothes washer, less than 80 lbs (36.3 kg) 9 gallons/cf/cycle 1,200 liters/m3/cycle
Commercial dishwasher
    Under counter, high temperature 1.98 gallons/rack 7.50  liters/rack
    Under counter, low temperature 1.95 gallons/rack 7.38 liters/rack
    Door type, high temperature 1.44 gallons/rack 5.45 liters/rack
    Door type, low temperature 1.85 gallons/rack 7.00 liters/rack
    Single tank rack conveyor, high temperature 1.13 gallons/rack 4.28 liters/rack
    Single tank rack conveyor, low temperature 1.23 gallons/rack 4.66 liters/rack
    Multi- tank rack conveyor, high temperature 1.1 gallons/rack 4.16 liters/rack
    Multi- tank rack conveyor, low temperature 0.99 gallon/rack 3.75 liters/rack
    Flight type 180 gph 681.37 lph
Commercial ice machines
    Ice machine, IMH (ice-making head) H < 450 lbs/day (<204.11 kg/day) < 25 gal/100 lbs ice < 95 liters/46 kg ice
    Ice machine, IMH (ice-making head)  H > 450 lbs/day (>204.11 kg/day) < 25 gal/100 lbs ice < 95 liters/46 kg ice
    Ice machine, RCU (no remote compressor) H < 1,000 lbs/day (<453.59 kg/day) < 25 gal/100 lbs ice < 95 liters/46 kg ice
    Ice machine, RCU (no remote compressor)  H > 1,000 lbs/day (>453.59 kg/day) < 25 gal/100 lbs ice < 95 liters/46 kg ice
    Ice machine, RCU (remote compressor)  H < 934 lbs/day (<423.66 kg/day) < 25 gal/100 lbs ice < 95 liters/46 kg ice
    Ice machine, RCU (remote compressor)  H > 934 lbs/day (>423.66 kg/day) < 25 gal/100 lbs ice < 95 liters/46 kg ice
    Ice machine, SCU (self-contained unit) < 35 gal/100 lbs ice < 133liters/46 kg ice
    Ice machine, water-cooled Must be on chilled loop Must be on chilled loop
    Ice machine, once-through water-cooled Banned Banned
Food steamer
    Steam cooker, batch cooking 8 gph/pan 3085.11 lph/pan
    Steam cooker, high production or cook to order 8 gph/pan 317.97 lph/pan
Combination oven  
    Countertop or stand mounted 40 gph 151.42 lph
    Roll-in 60 gph 227.12 lph
Other equipment Based on industry standards Based on industry standards
Notes: gph = gallons per hour; cf = cubic feet; lph = liters per hour; H = ice production.

For equipment not listed in the above tables, the project team may propose performance baseline requirements, with documentation supporting the proposed benchmark.

Alternative Compliance Paths (ACPs)

Europe ACP: Water Use Baseline

Projects in Europe may use the values defined by European Standards.

Reduce potable water use of indoor plumbing fixtures and fittings to a level equal to or below the LEED 2009 for Existing Buildings: Operations & Maintenance baseline, calculated assuming 100% of the building’s indoor plumbing fixtures and fittings meet the plumbing code requirements as stated in the 2006 editions of the Uniform Plumbing Code (UPC) or International Plumbing Code (IPC) pertaining to fixture and fitting performance [Europe ACP: UPC-IPC Equivalent] [India ACP: UPC-IPC Equivalent]. Fixtures and fittings included in the calculations for this credit are water closets, urinals, showerheads, faucets, faucet replacement aerators and metering faucets.

The LEED 2009 for Existing Buildings: Operations & Maintenance water use baseline is set depending on the year of substantial completion of the building’s indoor plumbing system. Substantial completion is defined as either initial building construction or the last plumbing renovation of all or part of the building that included 100% retrofit of all plumbing fixtures and fittings as part of the renovation. Set the baseline as follows:

  • For a plumbing system substantially completed in 1994 or later throughout the building, the baseline is 120% of the water use that would result if all fixtures met the codes cited above.
  • For a plumbing system substantially completed before 1994 throughout the building, the baseline is 160% of the water use that would result if all fixtures met the codes cited above.

If indoor plumbing systems were substantially completed at different times (because the plumbing renovations occurred at different times in different parts of the building), Set a whole-building average baseline by prorating between the above limits. Prorate based on the proportion of plumbing fixtures installed during the plumbing renovations in each date period, as explained in the LEED Reference Guide for Green Building Operations & Maintenance, 2009 Edition. Pre-1994 buildings that have had only minor fixture retrofits (e.g., aerators, showerheads, flushing valves) but no plumbing renovations in or after 1994 may use the 160% baseline for the whole building.

Demonstrate fixture and fitting performance through calculations to compare the water use of the as installed fixtures and fittings with the use of UPC- or IPC-compliant fixtures and fittings, or alternatives for Europe and India as explained in the LEED Reference Guide for Green Building Operations & Maintenance, 2009 Edition [Europe ACP: UPC-IPC Equivalent].

Develop and implement a policy requiring economic assessment of conversion to high-performance plumbing fixtures and fittings as part of any future indoor plumbing renovation. The assessment must account for potential water supply and disposal cost savings and maintenance cost savings [Europe ACP: UPC-IPC Equivalent].

Alternative Compliance Paths (ACPs)

Europe ACP: UPC-IPC Equivalent

Projects in Europe may use the values defined by European Standards.

India ACP: UPC-IPC Equivalent

Projects in India may use values defined by the 2011 UPC - India and the 2013 Green Plumbing Code Supplement – India.

Credit substitution available

You may use the LEED v4 version of this credit on v2009 projects. For more information check out this article.

During the performance period, have in place strategies and systems that in aggregate produce a reduction in indoor plumbing fixture and fitting potable water use from the calculated baseline established in WE Prerequisite 1: Minimum Indoor Plumbing Fixture and Fitting Efficiency.

The minimum water reduction percentage for each point threshold is as follows:

Percentage Reduction Points

10% 1

15% 2

20% 3

25% 4

30% 5

Alternative Compliance Paths (ACPs)

Credit substitution available

You may use the LEED v4 version of this credit on v2009 projects. For more information check out this article.

Employ strategies that in aggregate use less water than the water use baseline calculated for the building (not including irrigation). The minimum water savings percentage for each point threshold is as follows:

% Reduction Points
30% 2
35% 3
40% 4

Calculate the baseline according to the commercial and/or residential baselines outlined below1. Calculations are based on estimated occupant usage and must include only the following fixtures and fixture fittings (as applicable to the project scope): water closets, urinals, lavatory faucets, showers, kitchen sink faucets and pre-rinse spray valves. [Europe ACP: Water Use Baseline]

Commercial Fixtures, Fittings, and Appliances Current Baseline (Imperial Units) Current Baseline (Metric units)
Commercial Toilets 1.6 gallons per flush (gpf)*
Except blow-out fixtures: 3.5 (gpf)
6 liters per flush (lpf)
Except blow-out fixtures: 13 lpf
Commercial Urinals 1.0 (gpf) 4 lpf
Commercial Lavatory (Restroom) Faucets 2.2 gallons per minute (gpm) at 60 pounds per
square inch (psi), private applications only (hotel
or motel guest rooms, hospital patient rooms)
0.5 (gpm) at 60 (psi)** all others except private
applications
0.25 gallons per cycle for metering faucets
8.5 liters per minute (lpm) at 4 bar (58 psi),
private applications only (hotel or motel guest
rooms, hospital patient rooms)
2.0 lpm at 4 bar (58 psi), all others except
private applications
1 liter per cycle for metering faucets
Showerheads 2.5 (gpm) at 80 (psi) per shower stall **** 9.5 lpm at 5 bar (58 psi)
For projects with commercial pre-rinse spray valves, the flow rate must comply with the asME a112.18.1 standard of 1.6 gpm or less.

Residential fixtures, fittings, and appliances Current baseline (imperial units) Current baseline (metric units)
Residential toilets 1.6 (gpf)*** 6 liters per flush (lpf)
Except blow-out fixtures: 13 lpf
Residential lavatory (bathroom) faucets 2.2 (gpm) at 60 psi 4 lpm
8.5 lpm at 4 bar (58 psi), private applications only
(hotel or motel guest rooms, hospital patient rooms)
2.0 lpm at 4 bar (58 psi), all others except private
applications
1 liter per cycle for metering faucets
Residential kitchen faucet
Residential showerheads 2.5 (gpm) at 80 (psi) per shower stall**** flow rate ≤ 6.1 lpm
(no pressure specified; no performance requirement)
* EPAct1992 standard for toilets applies to both commercial and residential models.
** in addition to Epact requirements, the american society of Mechanical Engineers standard for public lavatory faucets is 0.5 gpm at 60 psi (2.0 lpm at 4 bar (58 psi)) (asME a112.18.1-2005). this maximum has been incorporated into the national uniform plumbing Code and the international plumbing Code.
*** EPAct 1992 standard for toilets applies to both commercial and residential models.
**** residential shower compartment (stall) in dwelling units: the total allowable flow rate from all flowing showerheads at any given time, including rain systems, waterfalls, bodysprays, bodyspas and jets, must be limited to the allowable showerhead flow rate as specified above (2.5 gpm) per shower compartment, where the floor area of the shower compartment is less than 2,500 square inches (1.5 square meters). for each increment of 2,500 square inches (1.5 square meters) of floor area thereafter or part thereof, an additional showerhead with total allowable flow rate from all flowing devices equal to or less than the allowable flow rate as specified above must be allowed. Exception: showers that emit recirculated nonpotable water originating from within the shower compartment while operating are allowed to exceed the maximum as long as the total potable water flow does not exceed the flow rate as specified above.

The following fixtures, fittings and appliances are outside the scope of the water use reduction calculation:

  • Commercial Steam Cookers
  • Commercial Dishwashers
  • Automatic Commercial Ice Makers
  • Commercial (family-sized) Clothes Washers
  • Residential Clothes Washers
  • Standard and Compact Residential Dishwashers

Alternative Compliance Paths (ACPs)

Europe ACP: Water Use Baseline

Projects in Europe may use the values defined by European Standards.

Project teams earn points by achieving the following percent reductions for both building water use and process water use. The minimum water savings percentage for each point threshold is as follows:

Percentage Reduction Points
30% 1
35% 2
40% 3

Building water use

Employ strategies that in aggregate use less water than the water use baseline calculated for the building (not including irrigation). The baseline shall meet the requirements of the Energy Policy Act (EPAct) of 1992 and subsequent rulings by the Department of Energy, requirements of the EPAct of 2005, and the plumbing code requirements as stated in the 2006 editions of the Uniform Plumbing Code or International Plumbing Code pertaining to fixture performance.

Calculations are based on estimated occupant usage and must include only the following fixtures and fixture fittings (as applicable to the project scope): water closets, urinals, lavatory faucets, showers, kitchen sink faucets and pre-rinse spray valves. Fixtures used for clinical use, such as surgical scrub sinks and exam room sinks are exempt from this calculation. [Europe ACP: Water Use Baseline]

Table 1: National efficiency baselines for commercial and residential water-using fixtures, fittings and appliances

Fixtures, Fittings, and Appliances Current Baseline (Imperial Units) Current Baseline (Metric Units)
Toilets 1.6 gallons per flush (gpf)* 6 liters per flush (lpf)
Urinals 1.0 (gpf) 4.0 lpf
Lavatory (restroom) faucets 2.2 gallons per minute (gpm) at 60 pounds per square inch (psi), private applications only
(e.g., hospital patient rooms)
0.5 (gpm) at 60 (psi)** all others except private applications
0.25 gallons per cycle for metering faucets
8.5 liters per minute (lpm) at 4 bar (58 psi), private applications only (e.g., hospital patient rooms)
2.0 lpm at 4 bar (58 psi), all others except private applications
1 liter per cycle for metering faucets
Pre-rinse spray valves
(for food service applications)
Flow rate ≤ 1.6 (gpm) Flow rate ≤ 6 liters per minute (lpm)
Showerheads 2.5 gpm at 80 psi per shower stall**** 9.5 lpm at 5.5 bar (80 psi) per shower stall
*        EPAct 1992 standard for toilets applies to both commercial and residential models.
**      In addition to EPAct requirements, the American Society of Mechanical Engineers standard for public lavatory faucets is 0.5 gpm at 60 psi (2.0 lpm at 4 bar (58 psi)) (ASME A112.18.1-2005). This maximum has been incorporated into the national Uniform Plumbing Code and the International Plumbing Code.
***    EPAct 1992 standard for toilets applies to both commercial and residential models.
****  Residential shower compartment (stall) in dwelling units: The total allowable flow rate from all flowing showerheads at any given time, including rain systems, waterfalls, bodysprays, bodyspas and jets, must be limited to the allowable showerhead flow rate as specified above (2.5 gpm/9.5 lpm) per shower compartment, where the floor area of the shower compartment is less than 2,500 square inches (1.5 square meters). For each increment of 2,500 square inches (1.5 square meters) of floor area thereafter or part thereof, an additional showerhead with total allowable flow rate from all flowing devices equal to or less than the allowable flow rate as specified above must be allowed. Exception: Showers that emit recirculated nonpotable water originating from within the shower compartment while operating are allowed to exceed the maximum as long as the total potable water flow does not exceed the flow rate as specified above.

AND
Process water use

Employ strategies that in aggregate use less water than the process water use baseline calculated for equipment performance requirements as listed in Table 2. Calculations are based on estimated occupant usage and shall include only the following fixtures (as applicable to the project scope): clothes washers, dishwashers, ice machines, food steamers and combination ovens.

Exemptions from calculations:

  • Appliances and equipment for which water is used toward human consumption may be excluded. For example, bread misters, soda machines, coffee making machines, misters for produce and fixtures used to fill sinks for washing produce.
  • Fixtures whose flow rates are regulated by health codes may be excluded from the calculation. For example, regulated medical equipment is excluded. See WE Prerequisite 2 for requirements applicable to heat rejecting medical equipment.

For applicable equipment not addressed in Tables 1 or 2, additional equipment performance baseline requirements may be proposed, provided that documentation supporting the proposed benchmark or industry standard is provided.

Table 2: Equipment performance requirements table

Equipment Baseline (Imperial Units) Baseline (Metric Units)
Commercial Clothes Washer – less than 80 lbs (36.3 kg) 9 gallon/CF/cycle 1,200 liters/m3/cycle
Commercial Dishwashers
Undercounter – high temp 1.98 gallon/rack 7.50 liters/rack
Undercounter – low temp 1.95 gallon/rack 7.38 liters/rack
Door type – high temp 1.44 gallon/rack 5.45 liters/rack
Door type – low temp 1.85 gallon/rack 7.00 liters/rack
Single tank rack conveyor – high temp 1.13 gallon/rack 4.28 liters/rack
Single tank rack conveyor – low temp 1.23 gallon/rack 4.66 liters/rack
Multi-tank rack conveyor – high temp 1.1 gallon/rack 4.16 liters/rack
Multi-tank rack conveyor – low temp 0.99 gallon/rack 3.75 liters/rack
Flight type 180 gallon/hour 681 liters/hour
Commercial Ice Machines
Water-cooled ice machine capacity < 450 lb/day (<204.11 kg/day) <25 gal/100 lb ice <95 liters/46 kg ice
Air-cooled ice machine capacity > 450 lb/day (>204.11 kg/day) <25 gal/100 lb ice <95 liters/46 kg ice
Air-cooled ice machine with remote condensing unit (w/o remote compressor) capacity < 1000 lb/day (<453.59 kg/day) <25 gal/100 lb ice <95 liters/46 kg ice
Air-cooled ice machine with remote condensing unit (w/o remote compressor) capacity > 1000 lb/day (>453.59 kg/day) <25 gal/100 lb ice <95 liters/46 kg ice
Air-cooled ice machine with remote condensing unit (with remote compressor) capacity < 934 lb/day (<423.66 kg/day) <25 gal/100 lb ice <95 liters/46 kg ice
Air-cooled ice machine with remote condensing unit (with remote compressor) capacity > 934 lb/day (>423.66 kg/day) <25 gal/100 lb ice <95 liters/46 kg ice
Air-cooled ice machine Self Contained Unit (SCU) <25 gal/100 lb ice <95 liters/46 kg ice
Water-cooled ice machines Must be on closed cooling loop Must be on closed cooling loop
Water-cooled ice machines once through cooling Not allowed Not allowed
Food Steamers
Boiler type steam cooker – batch cooking 8 gallon/hour/pan 30.28 liters/hour/pan
Boilerless type steam cooker – high production/cook to order 8 gallon/hour/pan 30.28 liters/hour/pan
Combination Oven 40 gph 151.42 lph
Countertop or stand mounted 40 gph 151.42 lph
Roll-in 60 gph 227.12 lph
Other equipment Performance baseline based on industry standards

Alternative Compliance Paths (ACPs)

Europe ACP: Water Use Baseline

Projects in Europe may use the values defined by European Standards.

Employ strategies that in aggregate use 20% less water than the water use baseline calculated for the building (not including irrigation) after meeting the Energy Policy Act of 1992 fixture performance requirements. Calculations are based on estimated occupant usage and shall include only the following fixtures (as applicable to the building): water closets, urinals, lavatory faucets, showers and kitchen sinks.

Employ strategies that in aggregate use 30% less water than the water use baseline calculated for the building (not including irrigation) after meeting the Energy Policy Act of 1992 fixture performance requirements. Calculations are based on estimated occupant usage and shall include only the following fixtures (as applicable to the building): water closets, urinals, lavatory faucets, showers and kitchen sinks.

Reduce potable water usage of indoor plumbing fixtures and fittings to a level equal to or below the LEED for Existing Buildings: O&M baseline, calculated assuming 100% of the building’s indoor plumbing fixtures and fittings meet the Uniform Plumbing Codes (UPC) 2006 or International Plumbing Codes (IPC) 2006 fixture and fitting performance requirements. Fixtures and fittings included in the calculations for this credit are water closets, urinals, showerheads, faucets, faucet replacement aerators and metering faucets.

The LEED for Existing Buildings: O&M baseline water usage is set depending on the year of substantial completion of the building’s indoor plumbing system. Substantial completion is defined as either initial building construction or the last plumbing renovation of all or part of the building that included 100% retrofit of all plumbing fixtures and fittings as part of the renovation. Set the baseline as follows:

  • For a plumbing system substantially completed in 1994 or later throughout the building, the baseline is 120% of the water usage that would result if all fixtures met the codes cited above.
  • For a plumbing system substantially completed before 1994 throughout the building, the baseline is 160% of the water usage that would result if all fixtures met the codes cited above.

If indoor plumbing systems were substantially completed at different times for different parts of the building because the plumbing renovations occurred at different times, set a whole-building average baseline by prorating between the above limits. Prorate based on the proportion of plumbing fixtures installed during the plumbing renovations in each date period, as explained in the LEED for Existing Buildings: Operations & Maintenance Reference Guide. Pre-1994 buildings that have had only minor fixture retrofits (aerators, showerheads, flushing valves) but no plumbing renovations after 1993 may use the 160% baseline for the whole building.

Demonstrate fixture and fitting performance through calculations to compare the water use of the as-installed fixtures and fittings with the use of UPC- or IPC-compliant fixtures and fittings, as explained in the LEED for Existing Buildings: Operations & Maintenance Reference Guide.

Develop and implement a policy requiring economic assessment of conversion to high-performance plumbing fixtures and fittings as part of any future indoor plumbing renovation. The assessment must account for potential water supply and disposal cost savings and maintenance cost savings.

Potable water is defined as water that is suitable for drinking and is supplied from wells or municipal water systems.

During the performance period, have in place strategies and systems that in aggregate produce a reduction in indoor plumbing fixture and fitting potable water use from the calculated LEED for Existing Buildings: O&M baseline established in WE Prerequisite 1.

  • WE Credit 2.1 (1 point): 10% reduction in indoor plumbing fixture and fitting potable water use from the LEED for Existing Buildings: O&M baseline.
  • WE Credit 2.2 (2 points): 20% reduction in indoor plumbing fixture and fitting potable water use from the LEED for Existing Buildings: O&M baseline.
  • WE Credit 2.3 (3 points): 30% reduction in indoor plumbing fixture and fitting potable water use from the LEED for Existing Buildings: O&M baseline.

Potable water is defined as water that is suitable for drinking and is supplied from wells or municipal water systems.

  • Based on tenant occupancy requirements, employ strategies that in aggregate use 20% less water than the water use baseline calculated for the tenant space (not including irrigation) after meeting Energy Policy Act of 1992 fixture performance requirements.

    • Based on tenant occupancy requirements, employ strategies that in aggregate use 30% less water than the water use baseline calculated for the tenant space (not including irrigation) after meeting Energy Policy Act of 1992 fixture performance requirements.

      For nonresidential buildings, mixed-use buildings, and multifamily residential buildings four stories or more:

      Indoor water usage in new buildings and buildings undergoing major renovations as part of the project must be an average 40% less than in baseline buildings. The baseline usage is based on the requirements of the United States Energy Policy Act of 1992 and subsequent rulings by the Department of Energy, the requirements of the Energy Policy Act of 2005, and the fixture performance standards in the 2006 editions of the Uniform Plumbing Code or International Plumbing Code as to fixture performance. Calculations are based on estimated occupant usage and include only the following fixtures and fixture fittings (as applicable to the project scope): water closets (toilets), urinals, lavatory faucets, showers, kitchen sink faucets, and prerinse spray valves.

      The water efficiency threshold is calculated as a weighted average of water usage for the buildings constructed as part of the project based on their conditioned area. Projects may also follow the LEED for Multiple Buildings and On-Campus Building Application Guide alternative calculation methodology to show compliance with this credit.

      Commercial Fixtures, Fittings, and Appliances Current Baseline (Imperial Units) Current Baseline (Metric units)
      Commercial Toilets 1.6 gallons per flush (gpf)*
      Except blow-out fixtures: 3.5 (gpf)
      6 liters per flush (lpf)
      Except blow-out fixtures: 13 lpf
      Commercial Urinals 1.0 (gpf) 4 lpf
      Commercial Lavatory (Restroom) Faucets 2.2 gallons per minute (gpm) at 60 pounds per
      square inch (psi), private applications only (hotel
      or motel guest rooms, hospital patient rooms)
      0.5 (gpm) at 60 (psi)** all others except private
      applications
      0.25 gallons per cycle for metering faucets
      8.5 liters per minute (lpm) at 4 bar (58 psi),
      private applications only (hotel or motel guest
      rooms, hospital patient rooms)
      2.0 lpm at 4 bar (58 psi), all others except
      private applications
      1 liter per cycle for metering faucets
      Showerheads 2.5 (gpm) at 80 (psi) per shower stall **** 9.5 lpm at 5 bar (58 psi)
      For projects with commercial pre-rinse spray valves, the flow rate must comply with the asME a112.18.1 standard of 1.6 gpm or less.

      Residential fixtures, fittings, and appliances Current baseline (imperial units) Current baseline (metric units)
      Residential toilets 1.6 (gpf)*** 6 liters per flush (lpf)
      Except blow-out fixtures: 13 lpf
      Residential lavatory (bathroom) faucets 2.2 (gpm) at 60 psi 4 lpm
      8.5 lpm at 4 bar (58 psi), private applications only
      (hotel or motel guest rooms, hospital patient rooms)
      2.0 lpm at 4 bar (58 psi), all others except private
      applications
      1 liter per cycle for metering faucets
      Residential kitchen faucet
      Residential showerheads 2.5 (gpm) at 80 (psi) per shower stall**** flow rate ≤ 6.1 lpm
      (no pressure specified; no performance requirement)
      * EPAct1992 standard for toilets applies to both commercial and residential models.
      ** in addition to Epact requirements, the american society of Mechanical Engineers standard for public lavatory faucets is 0.5 gpm at 60 psi (2.0 lpm at 4 bar (58 psi)) (asME a112.18.1-2005). this maximum has been incorporated into the national uniform plumbing Code and the international plumbing Code.
      *** EPAct 1992 standard for toilets applies to both commercial and residential models.
      **** residential shower compartment (stall) in dwelling units: the total allowable flow rate from all flowing showerheads at any given time, including rain systems, waterfalls, bodysprays, bodyspas and jets, must be limited to the allowable showerhead flow rate as specified above (2.5 gpm) per shower compartment, where the floor area of the shower compartment is less than 2,500 square inches (1.5 square meters). for each increment of 2,500 square inches (1.5 square meters) of floor area thereafter or part thereof, an additional showerhead with total allowable flow rate from all flowing devices equal to or less than the allowable flow rate as specified above must be allowed. Exception: showers that emit recirculated nonpotable water originating from within the shower compartment while operating are allowed to exceed the maximum as long as the total potable water flow does not exceed the flow rate as specified above.

      The following fixtures, fittings, and appliances are outside the scope of the water use reduction calculation:
      a. Commercial steam cookers.
      b. Commercial dishwashers.
      c. Automatic commercial ice makers.
      d. Commercial (family-sized) clothes washers.
      e. Residential clothes washers.
      f. Standard and compact residential dishwashers.

      AND
      For new single-family residential buildings and new multiunit residential buildings three stories or fewer, 90% of buildings must use a combination of fixtures that would earn 5 points under LEED for Homes 2008 WE Credit 3, Indoor Water Use.

      Reduce fixture potable water usage to a level equal to or below water use baseline, calculated as 120% of the water usage that would result if 100% of the total building fixture count were outfitted with plumbing fixtures that meet the Energy Policy Act of 1992 fixture performance requirements. If the building does not have separate metering for each water use (fixture use, process use, irrigation and other uses), the water use reduction achievements can be demonstrated with calculations. At least one meter for the overall building water use is required and metering for cooling towers and other process water uses are encouraged but not required.

      Have in place over the performance period strategies and systems that in aggregate produce a reduction of fixture potable water use from the calculated fixture water usage baseline established in WE Prerequisite 1. If the building does not have separate metering for each water use (fixture use, process use, irrigation and other uses), the water use reduction achievements can be demonstrated for WE 3.1 with calculations. At least one meter for the overall building water use is required and metering for cooling towers and other process water use encouraged but not required.

      To earn WE 3.2, measured fixture water use demonstrating required level of efficiency must be provided.

      • WE 3.1: 10% reduction in fixture water use from the baseline. (1 point)
      • WE 3.2: 20% reduction in fixture water use from the baseline. (1 point)

      Employ strategies that in aggregate use 20% less water than the water use baseline calculated for the building (not including irrigation) after meeting the Energy Policy Act of 1992 fixture performance requirements. Calculations are based on estimated occupant usage and shall include only the following fixtures (as applicable to the building): water closets, urinals, lavatory faucets, showers and kitchen sinks.

      Employ strategies that in aggregate use 30% (1 point) or 40% (2 points) less water than the water use baseline calculated for the building (not including irrigation) after meeting the Energy Policy Act of 1992 fixture performance requirements. Calculations are based on estimated occupant usage and shall include only the following fixtures (as applicable to the building): water closets, urinals, lavatory faucets, showers and kitchen sinks.

      Employ strategies that in aggregate use 20% less water than the water use baseline calculated for the building (not including irrigation) after meeting the Energy Policy Act of 1992 (and as amended) fixture performance requirements. Calculations are based on estimated occupant usage and shall include only the following fixtures (as applicable to the building): water closets, urinals, lavatory faucets, showers and kitchen sinks.

      Employ strategies that in aggregate use 30% less water than the water use baseline calculated for the building (not including irrigation) after meeting the Energy Policy Act of 1992 (and as amended) fixture performance requirements. Calculations are based on estimated occupant usage and shall include only the following fixtures (as applicable to the building): water closets, urinals, lavatory faucets, showers and kitchen sinks.

      Employ strategies that in aggregate use 20% less water than the water use baseline calculated for the building (not including irrigation) after meeting the Energy Policy Act of 1992 fixture performance requirements.

      1 point in addition to WE 3.1

      Employ strategies that in aggregate use 30% less water than the water use baseline calculated for the building (not including irrigation) after meeting the Energy Policy Act of 1992 fixture performance requirements.

      Building Water Use

      For the fixtures and fittings listed in Table 1, as applicable to the project scope, reduce aggregate water consumption by 20% from the baseline. Base calculations on the volumes and flow rates shown in Table 1.

      All newly installed toilets, urinals, private lavatory faucets, and showerheads that are eligible for labeling must be WaterSense labeled (or a local equivalent for projects outside the U.S.).

      Table 1. Baseline water consumption of fixtures and fittings

      Commercial Fixtures, Fittings, and Appliances Current Baseline (IP Units) Current Baseline (SI units)
      Water closets (toilets)* 1.6 gallons per flush (gpf) 6 liters per flush (lpf)
      Urinal* 1.0 (gpf) 3.8 lpf
      Public lavatory (restroom) faucet 0.5 gpm at 60 psi all others except private applications 1.9 lpm at 415 kPa, all others except private applications
      Private lavatory faucet* 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
      Kitchen faucet (excluding faucets used exclusively for filling operations) 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
      Showerhead* 2.5 gpm at 80 psi per shower stall 9.5 lpm at 550 kPa per shower stall
      * WaterSense label available for this product type
      gpf = gallons per flush
      gpm = gallons per minute
      psi = pounds per square inch
      lpf = liters per flush
      lpm = liters per minute
      kPa = kilopascals

      Appliance and process water use

      Install appliances, equipment, and processes within the project scope that meet the requirements listed in the tables below .

      Table 2. Standards for appliances

      Appliance Requirement
      Residential clothes washers ENERGY STAR or performance equivalent
      Commercial clothes washers CEE Tier 3A
      Residential dishwashers (standard and compact) ENERGY STAR or performance equivalent
      Prerinse spray valves ≤ 1.3 gpm (4.9 lpm)
      Ice machine ENERGY STAR or performance equivalent and use either air-cooled or closed-loop cooling, such as chilled or condenser water system

      gpm = gallons per minute
      lpm = liters per minute

      Table 3. Standards for processes

      Process Requirement
      Heat rejection and cooling No once-through cooling with potable water for any equipment or appliances that reject heat
      Cooling towers and evaporative condensers Equip with:
      • makeup water meters
      • conductivity controllers and overflow alarms
      • efficient drift eliminators that reduce drift to maximum of 0.002% of recirculated water volume for counterflow towers and 0.005% of recirculated water flow for cross-flow towers

      Credit 3.1 (1 point) Employ strategies that in aggregate use 20% less water than the water use baseline calculated for the building (not including irrigation) after meeting Energy Policy Act of 1992 fixture performance requirements.

      Credit 3.2 (1 point) Exceed the potable water use reduction by an additional 10% (30% total efficiency increase).

      Have in place over the performance period strategies and systems that in aggregate produce a reduction of fixture potable water use from the calculated fixture water usage baseline established in WE Prerequisite 1. If the building does not have separate metering for each water use (fixture use, process use, irrigation and other uses), the water use reduction achievements can be demonstrated for WE 3.1 with calculations. At least one meter for the overall building water use is required and metering for cooling towers and other process water use encouraged but not required.

      To earn WE 3.2, measured fixture water use demonstrating required level of efficiency must be provided.

      • WE 3.1: 10% reduction in fixture water use from the baseline. (1 point)
      • WE 3.2: 20% reduction in fixture water use from the baseline. (1 point)

      During the performance period, have in place strategies and systems that in aggregate produce a reduction in indoor plumbing fixture and fitting potable water use from the calculated LEED for Existing Buildings: O&M baseline established in WE Prerequisite 1.

      • WE Credit 2.1 (1 point): 10% reduction in indoor plumbing fixture and fitting potable water use from the LEED for Existing Buildings: O&M baseline.
      • WE Credit 2.2 (2 points): 20% reduction in indoor plumbing fixture and fitting potable water use from the LEED for Existing Buildings: O&M baseline.
      • WE Credit 2.3 (3 points): 30% reduction in indoor plumbing fixture and fitting potable water use from the LEED for Existing Buildings: O&M baseline.

      Potable water is defined as water that is suitable for drinking and is supplied from wells or municipal water systems.

      During the performance period, have in place strategies and systems that in aggregate produce a reduction in indoor plumbing fixture and fitting potable water use from the calculated LEED for Existing Buildings: O&M baseline established in WE Prerequisite 1.

      • WE Credit 2.1 (1 point): 10% reduction in indoor plumbing fixture and fitting potable water use from the LEED for Existing Buildings: O&M baseline.
      • WE Credit 2.2 (2 points): 20% reduction in indoor plumbing fixture and fitting potable water use from the LEED for Existing Buildings: O&M baseline.
      • WE Credit 2.3 (3 points): 30% reduction in indoor plumbing fixture and fitting potable water use from the LEED for Existing Buildings: O&M baseline.

      Potable water is defined as water that is suitable for drinking and is supplied from wells or municipal water systems.

      Building Water Use

      For the fixtures and fittings listed in Table 1, as applicable to the project scope, reduce aggregate water consumption by 20% from the baseline. Base calculations on the volumes and flow rates shown in Table 1.

      All newly installed toilets, urinals, private lavatory faucets, and showerheads that are eligible for labeling must be WaterSense labeled (or a local equivalent for projects outside the U.S.).

      Projects where fixtures or fixture fittings are not within the tenant spaces are exempt from this prerequisite.

      Table 1. Baseline water consumption of fixtures and fittings

      Commercial Fixtures, Fittings, and Appliances Current Baseline (IP Units) Current Baseline (SI units)
      Water closets (toilets)* 1.6 gallons per flush (gpf) 6 liters per flush (lpf)
      Urinal* 1.0 (gpf) 3.8 lpf
      Public lavatory (restroom) faucet 0.5 gpm at 60 psi all others except private applications 1.9 lpm at 415 kPa, all others except private applications
      Private lavatory faucet* 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
      Kitchen faucet (excluding faucets used exclusively for filling operations) 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
      Showerhead* 2.5 gpm at 80 psi per shower stall 9.5 lpm at 550 kPa per shower stall
      * WaterSense label available for this product type
      gpf = gallons per flush
      gpm = gallons per minute
      psi = pounds per square inch
      lpf = liters per flush
      lpm = liters per minute
      kPa = kilopascals

      Appliance and process water use

      Install appliances, equipment, and processes within the project scope that meet the requirements listed in the tables below .

      Table 2. Standards for appliances

      Appliance Requirement
      Residential clothes washers ENERGY STAR or performance equivalent
      Commercial clothes washers CEE Tier 3A
      Residential dishwashers (standard and compact) ENERGY STAR or performance equivalent
      Prerinse spray valves ≤ 1.3 gpm (4.9 lpm)
      Ice machine ENERGY STAR or performance equivalent and use either air-cooled or closed-loop cooling, such as chilled or condenser water system

      gpm = gallons per minute
      lpm = liters per minute

      Table 3. Standards for processes

      Process Requirement
      Heat rejection and cooling No once-through cooling with potable water for any equipment or appliances that reject heat
      Cooling towers and evaporative condensers Equip with:
      • makeup water meters
      • conductivity controllers and overflow alarms
      • efficient drift eliminators that reduce drift to maximum of 0.002% of recirculated water volume for counterflow towers and 0.005% of recirculated water flow for cross-flow towers

      Building Water Use

      For the fixtures and fittings listed in Table 1, as applicable to the project scope, reduce aggregate water consumption by 20% from the baseline. Base calculations on the volumes and flow rates shown in Table 1.

      All newly installed toilets, urinals, private lavatory faucets, and showerheads that are eligible for labeling must be WaterSense labeled (or a local equivalent for projects outside the U.S.).

      Projects where fixtures or fixture fittings are not within the tenant spaces are exempt from this prerequisite.

      Table 1. Baseline water consumption of fixtures and fittings

      Commercial Fixtures, Fittings, and Appliances Current Baseline (IP Units) Current Baseline (SI units)
      Water closets (toilets)* 1.6 gallons per flush (gpf) 6 liters per flush (lpf)
      Urinal* 1.0 (gpf) 3.8 lpf
      Public lavatory (restroom) faucet 0.5 gpm at 60 psi all others except private applications 1.9 lpm at 415 kPa, all others except private applications
      Private lavatory faucet* 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
      Kitchen faucet (excluding faucets used exclusively for filling operations) 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
      Showerhead* 2.5 gpm at 80 psi per shower stall 9.5 lpm at 550 kPa per shower stall
      * WaterSense label available for this product type
      gpf = gallons per flush
      gpm = gallons per minute
      psi = pounds per square inch
      lpf = liters per flush
      lpm = liters per minute
      kPa = kilopascals

      Appliance and process water use

      Install appliances, equipment, and processes within the project scope that meet the requirements listed in the tables below .

      Table 2. Standards for appliances

      Appliance Requirement
      Residential clothes washers ENERGY STAR or performance equivalent
      Commercial clothes washers CEE Tier 3A
      Residential dishwashers (standard and compact) ENERGY STAR or performance equivalent
      Prerinse spray valves ≤ 1.3 gpm (4.9 lpm)
      Ice machine ENERGY STAR or performance equivalent and use either air-cooled or closed-loop cooling, such as chilled or condenser water system

      gpm = gallons per minute
      lpm = liters per minute

      Table 3. Standards for processes

      Process Requirement
      Heat rejection and cooling No once-through cooling with potable water for any equipment or appliances that reject heat
      Cooling towers and evaporative condensers Equip with:
      • makeup water meters
      • conductivity controllers and overflow alarms
      • efficient drift eliminators that reduce drift to maximum of 0.002% of recirculated water volume for counterflow towers and 0.005% of recirculated water flow for cross-flow towers

      In addition, water-consuming appliances, equipment, and processes must meet the requirements listed in Tables 4 and 5.

      Table 4. Standards for appliances

      Kitchen equipment Requirement (IP units) Requirement (SI units)
      Dishwasher Undercounter ≤ 1.6 gal/rack ≤ 6.0 liters/rack
      Stationary, single tank, door ≤ 1.4 gal/rack ≤ 5.3 liters/rack
      Single tank, conveyor ≤ 1.0 gal/rack ≤ 3.8 liters/rack
      Multiple tank, conveyor ≤ 0.9 gal/rack ≤ 3.4liters/rack
      Flight machine ≤ 180 gal/hour ≤ 680 liters/hour
      Food steamer Batch ≤ 6 gal/hour/pan ≤ 23 liters/hour/pan
      Cook-to-order ≤ 10 gal/hour/pan ≤ 38 liters/hour/pan
      Combination oven Countertop or stand ≤ 3.5 gal/hour/pan ≤ 13 liters/hour/pan
      Roll-in ≤ 3.5 gal/hour/pan ≤ 13 liters/hour/pan

      Table 5. Standards for processes

      Process Requirement
      Discharge water temperature tempering Where local requirements limit discharge temperature of fluids into drainage system, use tempering device that runs water only when equipment discharges hot water
      OR
      Provide thermal recovery heat exchanger that cools drained discharge water below code-required maximum discharge temperatures while simultaneously preheating inlet makeup water
      OR
      If fluid is steam condensate, return it to boiler
      Venturi-type flow-through vacuum generators or aspirators Use no device that generates vacuum by means of water flow through device into drain

      Building Water Use

      For the fixtures and fittings listed in Table 1, as applicable to the project scope, reduce aggregate water consumption by 20% from the baseline. Base calculations on the volumes and flow rates shown in Table 1.

      All newly installed toilets, urinals, private lavatory faucets, and showerheads that are eligible for labeling must be WaterSense labeled (or a local equivalent for projects outside the U.S.).

      Table 1. Baseline water consumption of fixtures and fittings

      Commercial Fixtures, Fittings, and Appliances Current Baseline (IP Units) Current Baseline (SI units)
      Water closets (toilets)* 1.6 gallons per flush (gpf) 6 liters per flush (lpf)
      Urinal* 1.0 (gpf) 3.8 lpf
      Public lavatory (restroom) faucet 0.5 gpm at 60 psi all others except private applications 1.9 lpm at 415 kPa, all others except private applications
      Private lavatory faucet* 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
      Kitchen faucet (excluding faucets used exclusively for filling operations) 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
      Showerhead* 2.5 gpm at 80 psi per shower stall 9.5 lpm at 550 kPa per shower stall
      * WaterSense label available for this product type
      gpf = gallons per flush
      gpm = gallons per minute
      psi = pounds per square inch
      lpf = liters per flush
      lpm = liters per minute
      kPa = kilopascals

      Appliance and process water use

      Install appliances, equipment, and processes within the project scope that meet the requirements listed in the tables below .

      Table 2. Standards for appliances

      Appliance Requirement
      Residential clothes washers ENERGY STAR or performance equivalent
      Commercial clothes washers CEE Tier 3A
      Residential dishwashers (standard and compact) ENERGY STAR or performance equivalent
      Prerinse spray valves ≤ 1.3 gpm (4.9 lpm)
      Ice machine ENERGY STAR or performance equivalent and use either air-cooled or closed-loop cooling, such as chilled or condenser water system

      gpm = gallons per minute
      lpm = liters per minute

      Table 3. Standards for processes

      Process Requirement
      Heat rejection and cooling No once-through cooling with potable water for any equipment or appliances that reject heat
      Cooling towers and evaporative condensers Equip with:
      • makeup water meters
      • conductivity controllers and overflow alarms
      • efficient drift eliminators that reduce drift to maximum of 0.002% of recirculated water volume for counterflow towers and 0.005% of recirculated water flow for cross-flow towers

      In addition, water-consuming appliances, equipment, and processes must meet the requirements listed in Tables 4 and 5.

      Table 4. Standards for appliances

      Kitchen equipment Requirement (IP units) Requirement (SI units)
      Dishwasher Undercounter ≤ 1.6 gal/rack ≤ 6.0 liters/rack
      Stationary, single tank, door ≤ 1.4 gal/rack ≤ 5.3 liters/rack
      Single tank, conveyor ≤ 1.0 gal/rack ≤ 3.8 liters/rack
      Multiple tank, conveyor ≤ 0.9 gal/rack ≤ 3.4liters/rack
      Flight machine ≤ 180 gal/hour ≤ 680 liters/hour
      Food steamer Batch ≤ 6 gal/hour/pan ≤ 23 liters/hour/pan
      Cook-to-order ≤ 10 gal/hour/pan ≤ 38 liters/hour/pan
      Combination oven Countertop or stand ≤ 3.5 gal/hour/pan ≤ 13 liters/hour/pan
      Roll-in ≤ 3.5 gal/hour/pan ≤ 13 liters/hour/pan

      Table 5. Standards for processes

      Process Requirement
      Discharge water temperature tempering Where local requirements limit discharge temperature of fluids into drainage system, use tempering device that runs water only when equipment discharges hot water
      OR
      Provide thermal recovery heat exchanger that cools drained discharge water below code-required maximum discharge temperatures while simultaneously preheating inlet makeup water
      OR
      If fluid is steam condensate, return it to boiler
      Venturi-type flow-through vacuum generators or aspirators Use no device that generates vacuum by means of water flow through device into drain

      Option 1. Calculated Water Use
      Establishment

      For the indoor plumbing fixtures and fittings listed in Table 1, reduce water consumption to or below the LEED v4 for Existing Buildings: Operations & Maintenance baseline, calculated assuming 100% of the building’s indoor plumbing fixtures and fittings meet the flush and flow rates listed in Table 1.

      The LEED v4 for Existing Buildings: Operations & Maintenance water use baseline is set depending on the year of building’s occupancy, as follows:

      • For a building with a certificate of occupancy dated 1995 or later, the baseline is 120% of the water use that would result if all fixtures met the code requirements in Table 1.
      • For a building with a certificate of occupancy dated before 1995, the baseline is 150% of the water use that would result if all fixtures met the code requirements in Table 1.
      Table 1. Fixture and fitting code requirements

      Commercial Fixtures, Fittings, and Appliances Current Baseline (IP Units) Current Baseline (SI units)
      Water closets (toilets)* 1.6 gallons per flush (gpf) 6 liters per flush (lpf)
      Urinal* 1.0 (gpf) 3.8 lpf
      Public lavatory (restroom) faucet 0.5 gpm at 60 psi all others except private applications 1.9 lpm at 415 kPa, all others except private applications
      Private lavatory faucet* 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
      Kitchen faucet (excluding faucets used exclusively for filling operations) 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
      Showerhead* 2.5 gpm at 80 psi per shower stall 9.5 lpm at 550 kPa per shower stall
      * WaterSense label available for this product type
      gpf = gallons per flush
      gpm = gallons per minute
      psi = pounds per square inch
      lpf = liters per flush
      lpm = liters per minute
      kPa = kilopascals

      If indoor plumbing systems were renovated after initial occupancy of the building, set a whole-building average baseline by prorating the above limits, based on the proportion of plumbing fixtures installed during the plumbing renovations in each period. Pre-1995 buildings that have had only minor fixture retrofits (e.g., aerators, showerheads, flushing valves) but no plumbing renovations in or after 1995 may use the 150% baseline for the whole building.

      Calculate fixture and fitting performance to compare the water use of the as-installed fixtures and fittings with the use of Uniform Plumbing Code or International Plumbing Code-compliant (baseline) fixtures and fittings.

      Inspect all existing fittings or fixtures to ensure they are operating properly. Make any repairs needed to bring all fixtures into good working order or permanently turn off water supply to nonfunctional units.

      Implement a fixture and fitting replacement and retrofit policy specifying that all newly installed toilets, urinals, private lavatory faucets, and showerheads that are eligible for labeling be WaterSense labeled (or a local equivalent for projects outside the U.S.).

      Performance

      For building water use, confirm that calculations are up to date. Demonstrate that all applicable purchases made during the performance period meet the requirements of the fixture and fitting replacement and retrofit policy.

      Option 2. Metered water use
      Establishment

      Meter fixtures and fittings and record metered data for one year to establish a water-use baseline.

      Performance

      For projects with at least 80% of fixtures and fittings metered, show that the water-use baseline has been maintained.

      Option 1. Calculated Water Use
      Establishment

      For the indoor plumbing fixtures and fittings listed in Table 1, reduce water consumption to or below the LEED v4 for Existing Buildings: Operations & Maintenance baseline, calculated assuming 100% of the building’s indoor plumbing fixtures and fittings meet the flush and flow rates listed in Table 1.

      The LEED v4 for Existing Buildings: Operations & Maintenance water use baseline is set depending on the year of building’s occupancy, as follows:

      • For a building with a certificate of occupancy dated 1995 or later, the baseline is 120% of the water use that would result if all fixtures met the code requirements in Table 1.
      • For a building with a certificate of occupancy dated before 1995, the baseline is 150% of the water use that would result if all fixtures met the code requirements in Table 1.
      Table 1. Fixture and fitting code requirements

      Commercial Fixtures, Fittings, and Appliances Current Baseline (IP Units) Current Baseline (SI units)
      Water closets (toilets)* 1.6 gallons per flush (gpf) 6 liters per flush (lpf)
      Urinal* 1.0 (gpf) 3.8 lpf
      Public lavatory (restroom) faucet 0.5 gpm at 60 psi all others except private applications 1.9 lpm at 415 kPa, all others except private applications
      Private lavatory faucet* 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
      Kitchen faucet (excluding faucets used exclusively for filling operations) 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
      Showerhead* 2.5 gpm at 80 psi per shower stall 9.5 lpm at 550 kPa per shower stall
      * WaterSense label available for this product type
      gpf = gallons per flush
      gpm = gallons per minute
      psi = pounds per square inch
      lpf = liters per flush
      lpm = liters per minute
      kPa = kilopascals

      If indoor plumbing systems were renovated after initial occupancy of the building, set a whole-building average baseline by prorating the above limits, based on the proportion of plumbing fixtures installed during the plumbing renovations in each period. Pre-1995 buildings that have had only minor fixture retrofits (e.g., aerators, showerheads, flushing valves) but no plumbing renovations in or after 1995 may use the 150% baseline for the whole building.

      Calculate fixture and fitting performance to compare the water use of the as-installed fixtures and fittings with the use of Uniform Plumbing Code or International Plumbing Code-compliant (baseline) fixtures and fittings.

      Inspect all existing fittings or fixtures to ensure they are operating properly. Make any repairs needed to bring all fixtures into good working order or permanently turn off water supply to nonfunctional units.

      Implement a fixture and fitting replacement and retrofit policy specifying that all newly installed toilets, urinals, private lavatory faucets, and showerheads that are eligible for labeling be WaterSense labeled (or a local equivalent for projects outside the U.S.).

      Have in place a process and appliance water equipment purchasing policy for the building and site addressing the products listed in Table 2. The policy must cover at least those products purchased within the building and site management’s control.

      Table 2. Standards for appliances

      Appliance Requirement
      Residential clothes washers ENERGY STAR or performance equivalent
      Commercial clothes washers CEE Tier 3A
      Residential dishwashers (standard and compact) ENERGY STAR or performance equivalent
      Prerinse spray valves ≤ 1.3 gpm (4.9 lpm)
      Ice machine ENERGY STAR or performance equivalent and use either air-cooled or closed-loop cooling, such as chilled or condenser water system

      gpm = gallons per minute
      lpm = liters per minute

      Performance

      For building water use, confirm that calculations are up to date. Demonstrate that all applicable purchases made during the performance period meet the requirements of the fixture and fitting replacement and retrofit policy.

      For appliances, demonstrate that appliances purchased and installed within the building meet the requirements listed in Table 2. Appliances not listed are not subject to any additional requirements.

      Option 2. Metered water use
      Establishment

      Meter fixtures and fittings and record metered data for one year to establish a water-use baseline.

      Performance

      For projects with at least 80% of fixtures and fittings metered, show that the water-use baseline has been maintained.

      Nonresidential buildings, mixed-use buildings, and multifamily residential buildings four stories or more

      For new buildings and buildings undergoing major renovations as part of the project, reduce indoor water usage by an average of 20% from a baseline. All newly installed toilets, urinals, private lavatory faucets, and showerheads that are eligible for labeling must be WaterSense labeled (or a local equivalent for projects outside the U.S.).

      For the fixtures and fittings listed in Table 1, as applicable to the project scope, reduce water consumption by 20% from the baseline. Base calculations on the volumes and flow rates shown in Table 1.

      The design case is calculated as a weighted average of water usage for the buildings constructed as part of the project based on their floor area.

      Table 1. Baseline water consumption of fixtures and fittings

      Commercial Fixtures, Fittings, and Appliances Current Baseline (IP Units) Current Baseline (SI units)
      Water closets (toilets)* 1.6 gallons per flush (gpf) 6 liters per flush (lpf)
      Urinal* 1.0 (gpf) 3.8 lpf
      Public lavatory (restroom) faucet 0.5 gpm at 60 psi all others except private applications 1.9 lpm at 415 kPa, all others except private applications
      Private lavatory faucet* 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
      Kitchen faucet (excluding faucets used exclusively for filling operations) 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
      Showerhead* 2.5 gpm at 80 psi per shower stall 9.5 lpm at 550 kPa per shower stall
      * WaterSense label available for this product type
      gpf = gallons per flush
      gpm = gallons per minute
      psi = pounds per square inch
      lpf = liters per flush
      lpm = liters per minute
      kPa = kilopascals

      New single-family residential buildings and new multiunit residential buildings three stories or fewer

      90% of residential buildings must use a combination of fixtures and fittings that would earn 2 points under LEED v4 Building Design and Construction: Homes and Multifamily Lowrise WE Credit Indoor Water Use.

      Further reduce fixture and fitting water use from the calculated baseline in WE Prerequisite Indoor Water Use Reduction. Additional potable water savings can be earned above the prerequisite level using alternative water sources. Include fixtures and fittings necessary to meet the needs of the occupants. Some of these fittings and fixtures may be outside the tenant space (for Commercial Interiors) or project boundary (for New Construction). Points are awarded according to Table 1.

      Table 1. Points for reducing water use

      Percentage reduction Points (BD&C) Points (Schools, Retail, Hospitality, Healthcare) Points (ID&C) Points (CI Retail) Points (CI Hospitality)
      25% 1 1 2 2 2
      30% 2 2 4 4 4
      35% 3 3 6 6 6
      40% 4 4 8 8 8
      45% 5 5 10 10 10
      50% 6 -- 12 -- 11

      Option 1. Calculated water use (1–5 points except Data Centers, 1–4 points Data Centers)
      Establishment

      None.

      Performance

      Have fixtures that use less water than the baseline calculated in WE Prerequisite Indoor Water-Use Reduction. Points are awarded according to Table 1.

      Table 1. Points for reducing calculated water use beyond the prerequisite level.

      Additional percentage reduction Points (except data centers) Points (data centers)
      10% 1 1
      15% 2 2
      20% 3 3
      25% 4 4
      30% 5 --

      Confirm that calculations are up to date. Demonstrate that all purchases made since the end of the performance period meet the design performance requirements.

      OR

      Option 2. Metered water use (1-5 points except Data Centers, 1-4 points Data Centers)
      Establishment

      Meter fixtures and fittings, and record meter data for one year to establish a water-use baseline.

      Performance

      For projects with at least 80% of fixtures and fittings metered, show a reduction from the baseline year of meter data.

      Table 2. Points for reducing metered water use

      Percentage reduction Points (except data centers) Points (data centers)
      < 5% 1 1
      5-10% 2 2
      10-15% 3 3
      15-20% 4 4
      >20% 5 --

      Option 1. Calculated water use (1–5 points except Data Centers, 1–4 points Data Centers)
      Establishment

      None.

      Performance

      Have fixtures that use less water than the baseline calculated in WE Prerequisite Indoor Water-Use Reduction. Points are awarded according to Table 1.

      Table 1. Points for reducing calculated water use beyond the prerequisite level.

      Additional percentage reduction Points (except data centers) Points (data centers)
      10% 1 1
      15% 2 2
      20% 3 3
      25% 4 4
      30% 5 --

      Confirm that calculations are up to date. Demonstrate that all purchases made since the end of the performance period meet the design performance requirements.

      OR

      Option 2. Metered water use (1-5 points except Data Centers, 1-4 points Data Centers)
      Establishment

      Meter fixtures and fittings, and record meter data for one year to establish a water-use baseline.

      Performance

      For projects with at least 80% of fixtures and fittings metered, show a reduction from the baseline year of meter data.

      Table 2. Points for reducing metered water use

      Percentage reduction Points (except data centers) Points (data centers)
      < 5% 1 1
      5-10% 2 2
      10-15% 3 3
      15-20% 4 4
      >20% 5 --

      Nonresidential buildings, mixed-use buildings, and multifamily residential buildings four stories or more

      For new buildings and buildings undergoing major renovations as part of the project, reduce indoor water usage by an average of 40% from a baseline
      All newly installed toilets, urinals, private lavatory faucets, and showerheads that are eligible for labeling must be WaterSense labeled (or local equivalent for projects outside the U.S.).
      For fixtures and fittings listed in Table 1, as applicable to the project scope, calculate the baseline water consumption using estimated occupant usage.

      The design case is calculated as a weighted average of water usage for the buildings constructed as part of the project, based on their floor area.

      Table 1. Baseline water consumption of fixtures and fittings

      Commercial Fixtures, Fittings, and Appliances Current Baseline (IP Units) Current Baseline (SI units)
      Water closets (toilets)* 1.6 gallons per flush (gpf) 6 liters per flush (lpf)
      Urinal* 1.0 (gpf) 3.8 lpf
      Public lavatory (restroom) faucet 0.5 gpm at 60 psi all others except private applications 1.9 lpm at 415 kPa, all others except private applications
      Private lavatory faucet* 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
      Kitchen faucet (excluding faucets used exclusively for filling operations) 2.2 gpm at 60 psi 8.3 lpm at 415 kPa
      Showerhead* 2.5 gpm at 80 psi per shower stall 9.5 lpm at 550 kPa per shower stall
      * WaterSense label available for this product type
      gpf = gallons per flush
      gpm = gallons per minute
      psi = pounds per square inch
      lpf = liters per flush
      lpm = liters per minute
      kPa = kilopascals

      New single-family residential buildings and new multiunit residential buildings three stories or fewer

      90% of buildings must use a combination of fixtures and fittings that would earn 4 points under LEED for Homes v4 WE Credit Indoor Water Use.

      Further reduce fixture and fitting water use from the calculated baseline in WE Prerequisite Indoor Water Use Reduction. Additional potable water savings can be earned above the prerequisite level using alternative water sources. Include fixtures and fittings necessary to meet the needs of the occupants. Some of these fittings and fixtures may be outside the tenant space (for Commercial Interiors) or project boundary (for New Construction). Points are awarded according to Table 1.

      Table 1. Points for reducing water use

      Percentage reduction Points (BD&C) Points (Schools, Retail, Hospitality, Healthcare) Points (ID&C) Points (CI Retail) Points (CI Hospitality)
      25% 1 1 2 2 2
      30% 2 2 4 4 4
      35% 3 3 6 6 6
      40% 4 4 8 8 8
      45% 5 5 10 10 10
      50% 6 -- 12 -- 11

      Meet the percentage reduction requirements above.

      AND
      Appliance and process water

      Install equipment within the project scope that meets the minimum requirements in Table 2, 3, 4, or 5 . One point is awarded for meeting all applicable requirements in any one table. All applicable equipment listed in each table must meet the standard.

      Schools, Retail, and Healthcare projects can earn a second point for meeting the requirements of two tables.

      Table 2. Compliant commercial washing machines

      To use Table 2, the project must process at least 120,000 lbs (57 606 kg) of laundry per year.

      Washing machine Requirement (IP units) Requirement (SI units)
      On-premise, minimum capacity 2,400 lbs (10 886 kg) per 8-hour shift Maximum 1.8 gals per pound * Maximum 7 liters per 0.45 kilograms *

      * Based on equal quantities of heavy, medium, and light soil laundry.

      Table 3. Standards for commercial kitchen equipment

      To use Table 3, the project must serve at least 100 meals per day of operation. All process and appliance equipment listed in the category of kitchen equipment and present on the project must comply with the standards.

      Kitchen equipment Requirement (IP units) Requirement (SI units)
      Dishwasher Undercounter ENERGY STAR ENERGY STAR or performance equivalent
       Stationary, single tank, door ENERGY STAR ENERGY STAR or performance equivalent
      Single tank, conveyor ENERGY STAR ENERGY STAR or performance equivalent
      Multiple tank, conveyor ENERGY STAR ENERGY STAR or performance equivalent
      Flight machine ENERGY STAR ENERGY STAR or performance equivalent
      Food steamer Batch (no drain connection) ≤ 2 gal/hour/pan including condensate cooling water ≤ 7.5 liters/hour/pan including condensate cooling water
      Cook-to-order (with drain connection) ≤ 5 gal/hour/pan including condensate cooling water ≤ 19 liters/hour/pan including condensate cooling water
      Combination oven, Countertop or stand ≤ 1.5 gal/hour/panincluding condensate cooling water ≤ 5.7 liters/hour/pan including condensate cooling water
      Roll-in ≤ 1.5 gal/hour/pan including condensate cooling water ≤ 5.7 liters/hour/pan including condensate cooling water
      Food waste disposer Disposer 3-8 gpm, full load condition; 10 minute automatic shutoff or 1 gpm, no-load condition 11–30 lpm, full load condition; 10-min automatic shutoff or 3.8 lpm, no-load condition
      Scrap collector Maximum 2 gpm makeup water Maximum 7.6 lpm makeup water
      Pulper Maximum 2 gpm makeup water Maximum 7.6 lpm makeup water
      Strainer basket No additional water usage No additional water usage

      gpm = gallons per minute
      gph = gallons per hour
      lpm = liters per minute
      lph = liters per hour

      Table 4. Compliant laboratory and medical equipment

      To use Table 4, the project must be a medical or laboratory facility.

      Lab equipment Requirement (IP units) Requirement (SI units)
      Reverse-osmosis water purifier 75% recovery 75% recovery
      Steam sterilizer For 60-inch sterilizer, 6.3 gal/U.S. tray
      For 48-inch sterilizer, 7.5 gal/U.S. tray
      For 1520-mm sterilizer, 28.5 liters/DIN tray
      For 1220-mm sterilizer, 28.35 liters/DIN tray
      Sterile process washer 0.35 gal/U.S. tray 1.3 liters/DIN tray
      X-ray processor, 150 mm or more in any dimension Film processor water recycling unit
      Digital imager, all sizes No water use

      Table 5. Compliant municipal steam systems

      To use Table 5, the project must be connected to a municipal or district steam system that does not allow the return of steam condensate.

      Steam system Standard
      Steam condensate disposal Cool municipally supplied steam condensate (no return) to drainage system with heat recovery system or reclaimed water
      OR
      Reclaim and use steam condensate 100% recovery and reuse

      Further reduce fixture and fitting water use from the calculated baseline in WE Prerequisite Indoor Water Use Reduction. Additional potable water savings can be earned above the prerequisite level using alternative water sources. Include fixtures and fittings necessary to meet the needs of the occupants. Some of these fittings and fixtures may be outside the tenant space (for Commercial Interiors) or project boundary (for New Construction). Points are awarded according to Table 1.

      Table 1. Points for reducing water use

      Percentage reduction Points (BD&C) Points (Schools, Retail, Hospitality, Healthcare) Points (ID&C) Points (CI Retail) Points (CI Hospitality)
      25% 1 1 2 2 2
      30% 2 2 4 4 4
      35% 3 3 6 6 6
      40% 4 4 8 8 8
      45% 5 5 10 10 10
      50% 6 -- 12 -- 11

      Further reduce fixture and fitting water use from the calculated baseline in WE Prerequisite Indoor Water Use Reduction. Additional potable water savings can be earned above the prerequisite level using alternative water sources. Include fixtures and fittings necessary to meet the needs of the occupants. Some of these fittings and fixtures may be outside the tenant space (for Commercial Interiors) or project boundary (for New Construction). Points are awarded according to Table 1.

      Table 1. Points for reducing water use

      Percentage reduction Points (BD&C) Points (Schools, Retail, Hospitality, Healthcare) Points (ID&C) Points (CI Retail) Points (CI Hospitality)
      25% 1 1 2 2 2
      30% 2 2 4 4 4
      35% 3 3 6 6 6
      40% 4 4 8 8 8
      45% 5 5 10 10 10
      50% 6 -- 12 -- 11

      Meet the percentage reduction requirements above.

      AND
      Appliance and process water

      Install equipment within the project scope that meets the minimum requirements in Table 2, 3, 4, or 5 . One point is awarded for meeting all applicable requirements in any one table. All applicable equipment listed in each table must meet the standard.

      Retail projects can earn a second point for meeting the requirements of two tables.

      Table 2. Compliant commercial washing machines

      To use Table 2, the project must process at least 120,000 lbs (57 606 kg) of laundry per year.

      Washing machine Requirement (IP units) Requirement (SI units)
      On-premise, minimum capacity 2,400 lbs (10 886 kg) per 8-hour shift Maximum 1.8 gals per pound * Maximum 7 liters per 0.45 kilograms *

      * Based on equal quantities of heavy, medium, and light soil laundry.

      Table 3. Standards for commercial kitchen equipment

      To use Table 3, the project must serve at least 100 meals per day of operation. All process and appliance equipment listed in the category of kitchen equipment and present on the project must comply with the standards.

      Kitchen equipment Requirement (IP units) Requirement (SI units)
      Dishwasher Undercounter ENERGY STAR ENERGY STAR or performance equivalent
       Stationary, single tank, door ENERGY STAR ENERGY STAR or performance equivalent
      Single tank, conveyor ENERGY STAR ENERGY STAR or performance equivalent
      Multiple tank, conveyor ENERGY STAR ENERGY STAR or performance equivalent
      Flight machine ENERGY STAR ENERGY STAR or performance equivalent
      Food steamer Batch (no drain connection) ≤ 2 gal/hour/pan including condensate cooling water ≤ 7.5 liters/hour/pan including condensate cooling water
      Cook-to-order (with drain connection) ≤ 5 gal/hour/pan including condensate cooling water ≤ 19 liters/hour/pan including condensate cooling water
      Combination oven, Countertop or stand ≤ 1.5 gal/hour/panincluding condensate cooling water ≤ 5.7 liters/hour/pan including condensate cooling water
      Roll-in ≤ 1.5 gal/hour/pan including condensate cooling water ≤ 5.7 liters/hour/pan including condensate cooling water
      Food waste disposer Disposer 3-8 gpm, full load condition; 10 minute automatic shutoff or 1 gpm, no-load condition 11–30 lpm, full load condition; 10-min automatic shutoff or 3.8 lpm, no-load condition
      Scrap collector Maximum 2 gpm makeup water Maximum 7.6 lpm makeup water
      Pulper Maximum 2 gpm makeup water Maximum 7.6 lpm makeup water
      Strainer basket No additional water usage No additional water usage

      gpm = gallons per minute
      gph = gallons per hour
      lpm = liters per minute
      lph = liters per hour

      Table 4. Compliant laboratory and medical equipment

      To use Table 4, the project must be a medical or laboratory facility.

      Lab equipment Requirement (IP units) Requirement (SI units)
      Reverse-osmosis water purifier 75% recovery 75% recovery
      Steam sterilizer For 60-inch sterilizer, 6.3 gal/U.S. tray
      For 48-inch sterilizer, 7.5 gal/U.S. tray
      For 1520-mm sterilizer, 28.5 liters/DIN tray
      For 1220-mm sterilizer, 28.35 liters/DIN tray
      Sterile process washer 0.35 gal/U.S. tray 1.3 liters/DIN tray
      X-ray processor, 150 mm or more in any dimension Film processor water recycling unit
      Digital imager, all sizes No water use

      Table 5. Compliant municipal steam systems

      To use Table 5, the project must be connected to a municipal or district steam system that does not allow the return of steam condensate.

      Steam system Standard
      Steam condensate disposal Cool municipally supplied steam condensate (no return) to drainage system with heat recovery system or reclaimed water
      OR
      Reclaim and use steam condensate 100% recovery and reuse

      Further reduce fixture and fitting water use from the calculated baseline in WE Prerequisite Indoor Water Use Reduction. Additional potable water savings can be earned above the prerequisite level using alternative water sources. Include fixtures and fittings necessary to meet the needs of the occupants. Some of these fittings and fixtures may be outside the tenant space (for Commercial Interiors) or project boundary (for New Construction). Points are awarded according to Table 1.

      Table 1. Points for reducing water use

      Percentage reduction Points (BD&C) Points (Schools, Retail, Hospitality, Healthcare) Points (ID&C) Points (CI Retail) Points (CI Hospitality)
      25% 1 1 2 2 2
      30% 2 2 4 4 4
      35% 3 3 6 6 6
      40% 4 4 8 8 8
      45% 5 5 10 10 10
      50% 6 -- 12 -- 11

      Meet the percentage reduction requirements above.

      AND
      Appliance and process water

      Install equipment within the project scope that meets the minimum requirements in Table 2, 3, 4, or 5 . One point is awarded for meeting all applicable requirements in any one table. All applicable equipment listed in each table must meet the standard.

      Retail projects can earn a second point for meeting the requirements of two tables.

      Table 2. Compliant commercial washing machines

      To use Table 2, the project must process at least 120,000 lbs (57 606 kg) of laundry per year.

      Washing machine Requirement (IP units) Requirement (SI units)
      On-premise, minimum capacity 2,400 lbs (10 886 kg) per 8-hour shift Maximum 1.8 gals per pound * Maximum 7 liters per 0.45 kilograms *

      * Based on equal quantities of heavy, medium, and light soil laundry.

      Table 3. Standards for commercial kitchen equipment

      To use Table 3, the project must serve at least 100 meals per day of operation. All process and appliance equipment listed in the category of kitchen equipment and present on the project must comply with the standards.

      Kitchen equipment Requirement (IP units) Requirement (SI units)
      Dishwasher Undercounter ENERGY STAR ENERGY STAR or performance equivalent
       Stationary, single tank, door ENERGY STAR ENERGY STAR or performance equivalent
      Single tank, conveyor ENERGY STAR ENERGY STAR or performance equivalent
      Multiple tank, conveyor ENERGY STAR ENERGY STAR or performance equivalent
      Flight machine ENERGY STAR ENERGY STAR or performance equivalent
      Food steamer Batch (no drain connection) ≤ 2 gal/hour/pan including condensate cooling water ≤ 7.5 liters/hour/pan including condensate cooling water
      Cook-to-order (with drain connection) ≤ 5 gal/hour/pan including condensate cooling water ≤ 19 liters/hour/pan including condensate cooling water
      Combination oven, Countertop or stand ≤ 1.5 gal/hour/panincluding condensate cooling water ≤ 5.7 liters/hour/pan including condensate cooling water
      Roll-in ≤ 1.5 gal/hour/pan including condensate cooling water ≤ 5.7 liters/hour/pan including condensate cooling water
      Food waste disposer Disposer 3-8 gpm, full load condition; 10 minute automatic shutoff or 1 gpm, no-load condition 11–30 lpm, full load condition; 10-min automatic shutoff or 3.8 lpm, no-load condition
      Scrap collector Maximum 2 gpm makeup water Maximum 7.6 lpm makeup water
      Pulper Maximum 2 gpm makeup water Maximum 7.6 lpm makeup water
      Strainer basket No additional water usage No additional water usage

      gpm = gallons per minute
      gph = gallons per hour
      lpm = liters per minute
      lph = liters per hour

      Table 4. Compliant laboratory and medical equipment

      To use Table 4, the project must be a medical or laboratory facility.

      Lab equipment Requirement (IP units) Requirement (SI units)
      Reverse-osmosis water purifier 75% recovery 75% recovery
      Steam sterilizer For 60-inch sterilizer, 6.3 gal/U.S. tray
      For 48-inch sterilizer, 7.5 gal/U.S. tray
      For 1520-mm sterilizer, 28.5 liters/DIN tray
      For 1220-mm sterilizer, 28.35 liters/DIN tray
      Sterile process washer 0.35 gal/U.S. tray 1.3 liters/DIN tray
      X-ray processor, 150 mm or more in any dimension Film processor water recycling unit
      Digital imager, all sizes No water use

      Table 5. Compliant municipal steam systems

      To use Table 5, the project must be connected to a municipal or district steam system that does not allow the return of steam condensate.

      Steam system Standard
      Steam condensate disposal Cool municipally supplied steam condensate (no return) to drainage system with heat recovery system or reclaimed water
      OR
      Reclaim and use steam condensate 100% recovery and reuse

      Further reduce fixture and fitting water use from the calculated baseline in WE Prerequisite Indoor Water Use Reduction. Additional potable water savings can be earned above the prerequisite level using alternative water sources. Include fixtures and fittings necessary to meet the needs of the occupants. Some of these fittings and fixtures may be outside the tenant space (for Commercial Interiors) or project boundary (for New Construction). Points are awarded according to Table 1.

      Table 1. Points for reducing water use

      Percentage reduction Points (BD&C) Points (Schools, Retail, Hospitality, Healthcare) Points (ID&C) Points (CI Retail) Points (CI Hospitality)
      25% 1 1 2 2 2
      30% 2 2 4 4 4
      35% 3 3 6 6 6
      40% 4 4 8 8 8
      45% 5 5 10 10 10
      50% 6 -- 12 -- 11

      Meet the percentage reduction requirements above.

      AND
      Appliance and process water

      Install equipment within the project scope that meets the minimum requirements in Table 2, 3, 4, or 5 . One point is awarded for meeting all applicable requirements in any one table. All applicable equipment listed in each table must meet the standard.

      Schools, Retail, and Healthcare projects can earn a second point for meeting the requirements of two tables.

      Table 2. Compliant commercial washing machines

      To use Table 2, the project must process at least 120,000 lbs (57 606 kg) of laundry per year.

      Washing machine Requirement (IP units) Requirement (SI units)
      On-premise, minimum capacity 2,400 lbs (10 886 kg) per 8-hour shift Maximum 1.8 gals per pound * Maximum 7 liters per 0.45 kilograms *

      * Based on equal quantities of heavy, medium, and light soil laundry.

      Table 3. Standards for commercial kitchen equipment

      To use Table 3, the project must serve at least 100 meals per day of operation. All process and appliance equipment listed in the category of kitchen equipment and present on the project must comply with the standards.

      Kitchen equipment Requirement (IP units) Requirement (SI units)
      Dishwasher Undercounter ENERGY STAR ENERGY STAR or performance equivalent
       Stationary, single tank, door ENERGY STAR ENERGY STAR or performance equivalent
      Single tank, conveyor ENERGY STAR ENERGY STAR or performance equivalent
      Multiple tank, conveyor ENERGY STAR ENERGY STAR or performance equivalent
      Flight machine ENERGY STAR ENERGY STAR or performance equivalent
      Food steamer Batch (no drain connection) ≤ 2 gal/hour/pan including condensate cooling water ≤ 7.5 liters/hour/pan including condensate cooling water
      Cook-to-order (with drain connection) ≤ 5 gal/hour/pan including condensate cooling water ≤ 19 liters/hour/pan including condensate cooling water
      Combination oven, Countertop or stand ≤ 1.5 gal/hour/panincluding condensate cooling water ≤ 5.7 liters/hour/pan including condensate cooling water
      Roll-in ≤ 1.5 gal/hour/pan including condensate cooling water ≤ 5.7 liters/hour/pan including condensate cooling water
      Food waste disposer Disposer 3-8 gpm, full load condition; 10 minute automatic shutoff or 1 gpm, no-load condition 11–30 lpm, full load condition; 10-min automatic shutoff or 3.8 lpm, no-load condition
      Scrap collector Maximum 2 gpm makeup water Maximum 7.6 lpm makeup water
      Pulper Maximum 2 gpm makeup water Maximum 7.6 lpm makeup water
      Strainer basket No additional water usage No additional water usage

      gpm = gallons per minute
      gph = gallons per hour
      lpm = liters per minute
      lph = liters per hour

      Table 4. Compliant laboratory and medical equipment

      To use Table 4, the project must be a medical or laboratory facility.

      Lab equipment Requirement (IP units) Requirement (SI units)
      Reverse-osmosis water purifier 75% recovery 75% recovery
      Steam sterilizer For 60-inch sterilizer, 6.3 gal/U.S. tray
      For 48-inch sterilizer, 7.5 gal/U.S. tray
      For 1520-mm sterilizer, 28.5 liters/DIN tray
      For 1220-mm sterilizer, 28.35 liters/DIN tray
      Sterile process washer 0.35 gal/U.S. tray 1.3 liters/DIN tray
      X-ray processor, 150 mm or more in any dimension Film processor water recycling unit
      Digital imager, all sizes No water use

      Table 5. Compliant municipal steam systems

      To use Table 5, the project must be connected to a municipal or district steam system that does not allow the return of steam condensate.

      Steam system Standard
      Steam condensate disposal Cool municipally supplied steam condensate (no return) to drainage system with heat recovery system or reclaimed water
      OR
      Reclaim and use steam condensate 100% recovery and reuse

      Employ strategies that in aggregate use 20% less water than the water use baseline calculated for the building (not including irrigation).

      Calculate the baseline according to the commercial and/or residential baselines outlined below1. Calculations are based on estimated occupant usage and must include only the following fixtures and fixture fittings (as applicable to the project scope): water closets, urinals, lavatory faucets, showers, kitchen sink faucets and pre-rinse spray valves. [Europe ACP: Water Use Baseline]

      Commercial Fixtures, Fittings, and Appliances Current Baseline (Imperial Units) Current Baseline (Metric units)
      Commercial Toilets 1.6 gallons per flush (gpf)*
      Except blow-out fixtures: 3.5 (gpf)
      6 liters per flush (lpf)
      Except blow-out fixtures: 13 lpf
      Commercial Urinals 1.0 (gpf) 4 lpf
      Commercial Lavatory (Restroom) Faucets 2.2 gallons per minute (gpm) at 60 pounds per
      square inch (psi), private applications only (hotel
      or motel guest rooms, hospital patient rooms)
      0.5 (gpm) at 60 (psi)** all others except private
      applications
      0.25 gallons per cycle for metering faucets
      8.5 liters per minute (lpm) at 4 bar (58 psi),
      private applications only (hotel or motel guest
      rooms, hospital patient rooms)
      2.0 lpm at 4 bar (58 psi), all others except
      private applications
      1 liter per cycle for metering faucets
      Showerheads 2.5 (gpm) at 80 (psi) per shower stall **** 9.5 lpm at 5 bar (58 psi)
      For projects with commercial pre-rinse spray valves, the flow rate must comply with the asME a112.18.1 standard of 1.6 gpm or less.

      Residential fixtures, fittings, and appliances Current baseline (imperial units) Current baseline (metric units)
      Residential toilets 1.6 (gpf)*** 6 liters per flush (lpf)
      Except blow-out fixtures: 13 lpf
      Residential lavatory (bathroom) faucets 2.2 (gpm) at 60 psi 4 lpm
      8.5 lpm at 4 bar (58 psi), private applications only
      (hotel or motel guest rooms, hospital patient rooms)
      2.0 lpm at 4 bar (58 psi), all others except private
      applications
      1 liter per cycle for metering faucets
      Residential kitchen faucet
      Residential showerheads 2.5 (gpm) at 80 (psi) per shower stall**** flow rate ≤ 6.1 lpm
      (no pressure specified; no performance requirement)
      * EPAct1992 standard for toilets applies to both commercial and residential models.
      ** in addition to Epact requirements, the american society of Mechanical Engineers standard for public lavatory faucets is 0.5 gpm at 60 psi (2.0 lpm at 4 bar (58 psi)) (asME a112.18.1-2005). this maximum has been incorporated into the national uniform plumbing Code and the international plumbing Code.
      *** EPAct 1992 standard for toilets applies to both commercial and residential models.
      **** residential shower compartment (stall) in dwelling units: the total allowable flow rate from all flowing showerheads at any given time, including rain systems, waterfalls, bodysprays, bodyspas and jets, must be limited to the allowable showerhead flow rate as specified above (2.5 gpm) per shower compartment, where the floor area of the shower compartment is less than 2,500 square inches (1.5 square meters). for each increment of 2,500 square inches (1.5 square meters) of floor area thereafter or part thereof, an additional showerhead with total allowable flow rate from all flowing devices equal to or less than the allowable flow rate as specified above must be allowed. Exception: showers that emit recirculated nonpotable water originating from within the shower compartment while operating are allowed to exceed the maximum as long as the total potable water flow does not exceed the flow rate as specified above.

      The following fixtures, fittings and appliances are outside the scope of the water use reduction calculation:

      • Commercial Steam Cookers
      • Commercial Dishwashers
      • Automatic Commercial Ice Makers
      • Commercial (family-sized) Clothes Washers
      • Residential Clothes Washers
      • Standard and Compact Residential Dishwashers

      Alternative Compliance Paths (ACPs)

      Europe ACP: Water Use Baseline

      Projects in Europe may use the values defined by European Standards.

      Employ strategies that in aggregate use less water than the water use baseline calculated for the building (not including irrigation). The minimum water savings percentage for each point threshold is as follows:

      % Reduction Points
      30% 2
      35% 3
      40% 4

      Calculate the baseline according to the commercial and/or residential baselines outlined below1. Calculations are based on estimated occupant usage and must include only the following fixtures and fixture fittings (as applicable to the project scope): water closets, urinals, lavatory faucets, showers, kitchen sink faucets and pre-rinse spray valves. [Europe ACP: Water Use Baseline]

      Commercial Fixtures, Fittings, and Appliances Current Baseline (Imperial Units) Current Baseline (Metric units)
      Commercial Toilets 1.6 gallons per flush (gpf)*
      Except blow-out fixtures: 3.5 (gpf)
      6 liters per flush (lpf)
      Except blow-out fixtures: 13 lpf
      Commercial Urinals 1.0 (gpf) 4 lpf
      Commercial Lavatory (Restroom) Faucets 2.2 gallons per minute (gpm) at 60 pounds per
      square inch (psi), private applications only (hotel
      or motel guest rooms, hospital patient rooms)
      0.5 (gpm) at 60 (psi)** all others except private
      applications
      0.25 gallons per cycle for metering faucets
      8.5 liters per minute (lpm) at 4 bar (58 psi),
      private applications only (hotel or motel guest
      rooms, hospital patient rooms)
      2.0 lpm at 4 bar (58 psi), all others except
      private applications
      1 liter per cycle for metering faucets
      Showerheads 2.5 (gpm) at 80 (psi) per shower stall **** 9.5 lpm at 5 bar (58 psi)
      For projects with commercial pre-rinse spray valves, the flow rate must comply with the asME a112.18.1 standard of 1.6 gpm or less.

      Residential fixtures, fittings, and appliances Current baseline (imperial units) Current baseline (metric units)
      Residential toilets 1.6 (gpf)*** 6 liters per flush (lpf)
      Except blow-out fixtures: 13 lpf
      Residential lavatory (bathroom) faucets 2.2 (gpm) at 60 psi 4 lpm
      8.5 lpm at 4 bar (58 psi), private applications only
      (hotel or motel guest rooms, hospital patient rooms)
      2.0 lpm at 4 bar (58 psi), all others except private
      applications
      1 liter per cycle for metering faucets
      Residential kitchen faucet
      Residential showerheads 2.5 (gpm) at 80 (psi) per shower stall**** flow rate ≤ 6.1 lpm
      (no pressure specified; no performance requirement)
      * EPAct1992 standard for toilets applies to both commercial and residential models.
      ** in addition to Epact requirements, the american society of Mechanical Engineers standard for public lavatory faucets is 0.5 gpm at 60 psi (2.0 lpm at 4 bar (58 psi)) (asME a112.18.1-2005). this maximum has been incorporated into the national uniform plumbing Code and the international plumbing Code.
      *** EPAct 1992 standard for toilets applies to both commercial and residential models.
      **** residential shower compartment (stall) in dwelling units: the total allowable flow rate from all flowing showerheads at any given time, including rain systems, waterfalls, bodysprays, bodyspas and jets, must be limited to the allowable showerhead flow rate as specified above (2.5 gpm) per shower compartment, where the floor area of the shower compartment is less than 2,500 square inches (1.5 square meters). for each increment of 2,500 square inches (1.5 square meters) of floor area thereafter or part thereof, an additional showerhead with total allowable flow rate from all flowing devices equal to or less than the allowable flow rate as specified above must be allowed. Exception: showers that emit recirculated nonpotable water originating from within the shower compartment while operating are allowed to exceed the maximum as long as the total potable water flow does not exceed the flow rate as specified above.

      The following fixtures, fittings and appliances are outside the scope of the water use reduction calculation:

      • Commercial Steam Cookers
      • Commercial Dishwashers
      • Automatic Commercial Ice Makers
      • Commercial (family-sized) Clothes Washers
      • Residential Clothes Washers
      • Standard and Compact Residential Dishwashers

      Alternative Compliance Paths (ACPs)

      Europe ACP: Water Use Baseline

      Projects in Europe may use the values defined by European Standards.

      Employ strategies that in aggregate use 20% less water than the water use baseline calculated for the building (not including irrigation).

      Calculate the baseline according to the commercial and/or residential baselines outlined below15. Calculations are based on estimated occupant usage and must include only the following fixtures and fixture fittings (as applicable to the project scope): water closets, urinals, lavatory faucets, showers, kitchen sink faucets and prerinse spray valves.

      Commercial  Fixtures, Fittings and Appliances Current Baseline (Imperial units) Current Baseline (Metric units)
       
      Commercial toilets
      1.6 gallons per flush (GPF)*
      Except blow-out fixtures: 3.5 (GPF)
      6 liters per flush (LPF)
      Except blow-out fixtures: 13 LPF
      Commercial urinals 1.0 GPF 4 LPF
       
       
      Commercial lavatory (restroom) faucets
      2.2 gallons per minute (GPM) at 60 pounds per square inch (PSI), private applications only (hotel or motel guest rooms, hospital patient rooms)
      0.5 GPM at 60 PSI** all others except private applications
      0.25 gallons per cycle for metering faucets
      8.5 liters per minute (LPM) at 4 bar (58 PSI), private applications only (hotel or motel guest rooms, hospital patient rooms)
      2.0 LPM at 4 bar (58 PSI), all others except private applications
      1 liter per cycle for metering faucets
      Commercial prerinse spray valves (for food service applications) Flow rate ≤ 1.6 GPM
      (no pressure specified; no performance requirement)
      Flow rate ≤ 6.1 LPM
      (no pressure specified; no performance requirement)

      Residential Fixtures, Fittings, and Appliances Current Baseline (Imperial units) Current Baseline (Metric units)
      Residential toilets 1.6 GPF*** 6 liters per flush (LPF)
      Residential lavatory (bathroom) faucets  
      2.2 GPM at 60 psi
       
      8.5 LPM at 4 bar (58 PSI)
       
      Residential kitchen faucet
       
      Residential showerheads
       
      2.5 GPM at 80 PSI per shower stall****
      9.5 LPM at 5.5 bar (80 PSI) per shower stall
      *  EPAct 1992 standard for toilets applies to both commercial and residential models.
      ** In addition to EPAct requirements, the American Society of Mechanical Engineers standard for public lavatory faucets is 0.5 GPM at 60 PSI (2.0 LPM at 4 bar (58 PSI)) (ASME A112.18.1-2005). This maximum has been incorporated into the national Uniform Plumbing Code and the International Plumbing Code.
      ***       EPAct 1992 standard for toilets applies to both commercial and residential models.
      **** Residential shower compartment (stall) in dwelling units: The total allowable flow rate from all flowing showerheads at any given time, including rain systems, waterfalls, body sprays, body spas and jets, must be limited to the allowable showerhead flow rate as specified above (2.5 GPM) per shower compartment, where the floor area of the shower compartment is less than 2,500 square inches (1.5 square meters). For each increment of 2,500 square inches (1.5 square meters) of floor area thereafter or part thereof, an additional showerhead with total allowable flow rate from all flowing devices equal to or less than the allowable flow rate as specified above must be allowed. Exception: Showers that emit recirculated nonpotable water originating from within the shower compartment while operating are allowed to exceed the maximum as long as the total potable water flow does not exceed the flow rate as specified above.

      The following fixtures, fittings and appliances are outside the scope of the water use reduction calculation:

      • Commercial Steam Cookers
      • Commercial Dishwashers
      • Automatic Commercial Ice Makers
      • Commercial (family sized) Clothes Washers
      • Residential Clothes Washers
      • Standard and Compact Residential Dishwashers
      15 Tables adapted from information developed and summarized by the U.S. Environmental Protection Agency (EPA) Office of Water based on requirements of the Energy Policy Act (EPAct) of 1992 and subsequent rulings by the Department of Energy, requirements of the EPAct of 2005, and the plumbing code requirements as stated in the 2006 editions of the Uniform Plumbing Code or International Plumbing Code pertaining to fixture performance.

      Employ strategies that in aggregate use less water than the water use baseline calculated for the building (not including irrigation). The minimum water savings percentage for each point threshold is as follows:

      Percentage  Reduction Points
      30% 2
      35% 3
      40% 4

      Calculate the baseline according to the commercial and/or residential baselines outlined below.17 Calculations are based on estimated occupant usage and must include only the following fixtures and fixture fittings (as applicable to the project scope): water closets, urinals, lavatory faucets, showers, kitchen sink faucets and pre-rinse spray valves.

      Commercial  Fixtures, Fittings and Appliances Current Baseline (Imperial units) Current Baseline (Metric units)
       
      Commercial toilets
      1.6 gallons per flush (GPF)*
      Except blow-out fixtures: 3.5 (GPF)
      6 liters per flush (LPF)
      Except blow-out fixtures: 13 LPF
      Commercial urinals 1.0 GPF 4 LPF
       
       
      Commercial lavatory (restroom) faucets
      2.2 gallons per minute (GPM) at 60 pounds per square inch (PSI), private applications only (hotel or motel guest rooms, hospital patient rooms)
      0.5 GPM at 60 PSI** all others except private applications
      0.25 gallons per cycle for metering faucets
      8.5 liters per minute (LPM) at 4 bar (58 PSI), private applications only (hotel or motel guest rooms, hospital patient rooms)
      2.0 LPM at 4 bar (58 PSI), all others except private applications
      1 liter per cycle for metering faucets
      Commercial prerinse spray valves (for food service applications) Flow rate ≤ 1.6 GPM
      (no pressure specified; no performance requirement)
      Flow rate ≤ 6.1 LPM
      (no pressure specified; no performance requirement)

      Residential Fixtures, Fittings, and Appliances Current Baseline (Imperial units) Current Baseline (Metric units)
      Residential toilets 1.6 GPF*** 6 liters per flush (LPF)
      Residential lavatory (bathroom) faucets  
      2.2 GPM at 60 psi
       
      8.5 LPM at 4 bar (58 PSI)
       
      Residential kitchen faucet
       
      Residential showerheads
       
      2.5 GPM at 80 PSI per shower stall****
      9.5 LPM at 5.5 bar (80 PSI) per shower stall
      *  EPAct 1992 standard for toilets applies to both commercial and residential models.
      ** In addition to EPAct requirements, the American Society of Mechanical Engineers standard for public lavatory faucets is 0.5 GPM at 60 PSI (2.0 LPM at 4 bar (58 PSI)) (ASME A112.18.1-2005). This maximum has been incorporated into the national Uniform Plumbing Code and the International Plumbing Code.
      ***       EPAct 1992 standard for toilets applies to both commercial and residential models.
      **** Residential shower compartment (stall) in dwelling units: The total allowable flow rate from all flowing showerheads at any given time, including rain systems, waterfalls, body sprays, body spas and jets, must be limited to the allowable showerhead flow rate as specified above (2.5 GPM) per shower compartment, where the floor area of the shower compartment is less than 2,500 square inches (1.5 square meters). For each increment of 2,500 square inches (1.5 square meters) of floor area thereafter or part thereof, an additional showerhead with total allowable flow rate from all flowing devices equal to or less than the allowable flow rate as specified above must be allowed. Exception: Showers that emit recirculated nonpotable water originating from within the shower compartment while operating are allowed to exceed the maximum as long as the total potable water flow does not exceed the flow rate as specified above.

      The following fixtures, fittings and appliances are outside the scope of the water use reduction calculation:

      • Commercial Steam Cookers
      • Commercial Dishwashers
      • Automatic Commercial Ice Makers
      • Commercial (family sized) Clothes Washers
      • Residential Clothes Washers
      • Standard and Compact Residential Dishwashers
      15 Tables adapted from information developed and summarized by the U.S. Environmental Protection Agency (EPA) Office of Water based on requirements of the Energy Policy Act (EPAct) of 1992 and subsequent rulings by the Department of Energy, requirements of the EPAct of 2005, and the plumbing code requirements as stated in the 2006 editions of the Uniform Plumbing Code or International Plumbing Code pertaining to fixture performance.