Entry Type ID Date Applicable Rating System Primary Credit Inquiry (LIs) Ruling (LIs) Related Addenda/LIs Related Resources Campus Applicable Internationally Applicable Country Applicability Reference Guide (Addenda) Page (Addenda) Location (Addenda) Description of Change (Addenda) "Global ACP" "100001547" "2012-10-01" "Retail - New Construction, Commercial Interiors, Retail - Commercial Interiors" "None" "None" "X" "Green Interior Design and Construction, 2009 edition $ Green Interior Design and Construction, 2009 edition, updated June 2011 $ Retail Supplement to Green Interior Design and Construction, 2009 edition $ Retail Supplement to Green Building Design and Con" "CI RS 43, Retail CI RS 40, Retail NC RS 59" "Requirements" "The second new bullet should read: ""Filtration media is Class F5 or higher, as defined by CEN Standard EN 779-2002, Particulate air filters for general ventilation, Determination of the filtration performance""" "Global ACP" "100001548" "2012-10-01" "Retail - New Construction, Commercial Interiors, Retail - Commercial Interiors" "None" "None" "X" "Green Interior Design and Construction, 2009 edition $ Green Interior Design and Construction, 2009 edition, updated June 2011 $ Retail Supplement to Green Interior Design and Construction, 2009 edition $ Retail Supplement to Green Building Design and Con" "CI RS 43, Retail CI RS 40, Retail NC RS 59" "Requirements" "The third new bullet should read: ""Filtration media with a minimum dust spot efficiency of 30% or higher and greater than 90% arrestance on a particle size of 3-10 " "Global ACP" "100001544" "2012-10-01" "Retail - New Construction, Commercial Interiors, Retail - Commercial Interiors" "None" "None" "X" "Green Interior Design and Construction, 2009 edition $ Green Interior Design and Construction, 2009 edition, updated June 2011 $ Retail Supplement to Green Interior Design and Construction, 2009 edition $ Retail Supplement to Green Building Design and Con" "CI RS 43, Retail CI RS 40, Retail NC RS 59" "Requirements" "The third bullet should read as follows: ""If permanently installed air handlers are used during construction, filtration media must be used at each return air grille that meets one of the following criteria below. Replace all filtration media immediately prior to occupancy.""" "Global ACP" "100001545" "2012-10-01" "Retail - New Construction, Commercial Interiors, Retail - Commercial Interiors" "None" "None" "Green Interior Design and Construction, 2009 edition $ Green Interior Design and Construction, 2009 edition, updated June 2011 $ Retail Supplement to Green Interior Design and Construction, 2009 edition $ Retail Supplement to Green Building Design and Con" "CI RS 43, Retail CI RS 40, Retail NC RS 59" "Requirements" "Add three bullets, indented, below the third bullet." "Global ACP" "100001546" "2012-10-01" "Retail - New Construction, Commercial Interiors, Retail - Commercial Interiors" "None" "None" "X" "Green Interior Design and Construction, 2009 edition $ Green Interior Design and Construction, 2009 edition, updated June 2011 $ Retail Supplement to Green Interior Design and Construction, 2009 edition $ Retail Supplement to Green Building Design and Con" "CI RS 43, Retail CI RS 40, Retail NC RS 59" "Requirements" "The first new bullet should read: ""Filtration media with a minimum efficiency reporting value (MERV) of 8 as determined by ASHRAE Standard 52.2-1999 (with errata but without addenda)""" "Regional ACP" "100001904" "2014-07-01" "New Construction, Core and Shell, Schools - New Construction, Retail - New Construction, Healthcare, Commercial Interiors, Retail - Commercial Interiors" "None" "None" "X" "East Asia" "LEED FOR BUILDING DESIGN AND CONSTRUCTION 2009; LEED FOR INTERIOR DESIGN AND CONSTRUCTION 2009; LEED BD+C: HEALTHCARE 2009; LEED BD+C: RETAIL 2009; LEED ID+C: RETAIL 2009" "LEED BD+C: 453; LEED ID+C: 315; LEED BD+C-Healthcare: 223; LEED BD+C-Retail: 117; LEED ID+C Retail 105" "Requirements" "The third new bullet should read: “Projects in East Asia may use filtration media classified as medium efficiency (中效过滤器) or higher as defined by Chinese standard GB/T 14295-2008 (空气过滤器).”"