Entry Type ID Date Applicable Rating System Primary Credit Inquiry (LIs) Ruling (LIs) Related Addenda/LIs Related Resources Campus Applicable Internationally Applicable Country Applicability Reference Guide (Addenda) Page (Addenda) Location (Addenda) Description of Change (Addenda) "Rating System Correction" "100000834" "2011-02-02" "Healthcare" "EQc3.1 - Construction IAQ management plan - during construction" "None" "None" "" "72" "For all projects" "Replace the text of the second bullet under the bullet beginning with ""If permanently installed..."" with the following:\n\no" "Global ACP" "100001572" "2012-10-01" "Healthcare" "EQc3.1 - Construction IAQ management plan - during construction" "None" "None" "X" "Healthcare Supplement to Green Building Design and Construction, 2009 edition" "HC RS 73" "Requirements" "Add three bullets, indented, below the above bullet." "Global ACP" "100001571" "2012-10-01" "Healthcare" "EQc3.1 - Construction IAQ management plan - during construction" "None" "None" "X" "Healthcare Supplement to Green Building Design and Construction, 2009 edition" "HC RS 73" "Requirements" "The first indented bullet regarding permanently installed air handlers should read as follows: o ""Filtration media must be used at each return air grille that meets one of the following criteria below.""" "Global ACP" "100001573" "2012-10-01" "Healthcare" "EQc3.1 - Construction IAQ management plan - during construction" "None" "None" "X" "Healthcare Supplement to Green Building Design and Construction, 2009 edition" "HC RS 73" "Requirements" "The first new bullet should read: ""Filtration media with a minimum efficiency reporting value (MERV) of 8 as determined by ASHRAE Standard 52.2-1999 (with errata but without addenda)""" "Global ACP" "100001574" "2012-10-01" "Healthcare" "EQc3.1 - Construction IAQ management plan - during construction" "None" "None" "X" "Healthcare Supplement to Green Building Design and Construction, 2009 edition" "HC RS 73" "Requirements" "The second new bullet should read: ""Filtration media is Class F5 or higher, as defined by CEN Standard EN 779-2002, Particulate air filters for general ventilation, Determination of the filtration performance""" "Global ACP" "100001575" "2012-10-01" "Healthcare" "EQc3.1 - Construction IAQ management plan - during construction" "None" "None" "X" "Healthcare Supplement to Green Building Design and Construction, 2009 edition" "HC RS 73" "Requirements" "The third new bullet should read: ""Filtration media with a minimum dust spot efficiency of 30% or higher and greater than 90% arrestance on a particle size of 3-10 " "Regional ACP" "100001904" "2014-07-01" "New Construction, Core and Shell, Schools - New Construction, Retail - New Construction, Healthcare, Commercial Interiors, Retail - Commercial Interiors" "EQc3.1 - Construction IAQ management plan - during construction" "None" "None" "X" "East Asia" "LEED FOR BUILDING DESIGN AND CONSTRUCTION 2009; LEED FOR INTERIOR DESIGN AND CONSTRUCTION 2009; LEED BD+C: HEALTHCARE 2009; LEED BD+C: RETAIL 2009; LEED ID+C: RETAIL 2009" "LEED BD+C: 453; LEED ID+C: 315; LEED BD+C-Healthcare: 223; LEED BD+C-Retail: 117; LEED ID+C Retail 105" "Requirements" "The third new bullet should read: “Projects in East Asia may use filtration media classified as medium efficiency (中效过滤器) or higher as defined by Chinese standard GB/T 14295-2008 (空气过滤器).”"