LEED O+M: Existing Buildings | v2009

Heat island effect - roof

SSc7.2 | Possible 1 point

Intent

To reduce heat islands1 to minimize impacts on microclimates and human and wildlife habitats.

Requirements

Option 1

Use roofing materials with a solar reflectance index (SRI)2 equal to or greater than the values in the table below for a minimum of 75% of the roof surface.

Roofing materials having a lower SIR value than those listed below ay be used if the weighted rooftop SRI average meets the following:

Area Roof Meeting Minimum SRI
————————————————
Total Roof Area

x SRI of Installed Roof
——————————

Required SRI

75%

Implement a maintenance program that ensures all SRI surfaces are cleaned at least every 2 years to maintain good reflectance.

OR

Option 2

Install and maintain a vegetated roof that covers at least 50% of the roof area.

OR

Option 3

Install high-albedo and vegetated roof surfaces that, in combination, meet the following criteria:

Area Roof Meeting Minimum SRI
————————————————
0.75

+ Area of Vegetated Roof
——————————

0.5

Total Roof Area

Roof Type Slope SRI
Low-sloped roof ≤ 2:12 78
Steep-sloped roof > 2:12 29

Alternatively, a weighted approach may be used to calculate compliance for multiple materials:

1 Heat islands are defined as thermal gradient differences between developed and underdeveloped areas.
2 The solar reflectance index (SRI) is a measure of the constructed surface's ability to reflect solar heat, as shown by a small temperature rise. It is defined so that a standardblack surface (reflectance 0.05, emittance 0.90) is 0 and a standard white surface (reflectance 0.80, emittance 0.90) is 100. to calculate the SRI for a given material, obtain the reflectance value and emittance value for the material. SRI is calculated according to ASTM E 1980. Reflectance is measured according to ASTM E 903, ASTM E 1918, or ASTM C 1549. Emittance is measured according to ASTM E408 or ASTM C 1371.
3 For the purposes of this credit, under cover parking is defined as parking underground, under desk, under roof, or under a building.
Credit substitution available

You may use the LEED v4 version of this credit on v2009 projects. For more information check out this article.

Join LEEDuser

Ask questions, share tips, and get notified of new forum posts by joining LEEDuser, a tool developed by BuildingGreen and supported by USGBC!

  • Share on Twitter
  • Share on Facebook
  • Share on LinkedIn
  • Print to PDF
Sample forms
Version: v03
Active Form Static Form
Version: v05
Active Form Static Form
View all sample forms

0 commentsLeave a comment

Leave a comment Don't have an account? Create one

You must be signed in to leave a comment.