LEED ID+C: Retail | v2009

Minimum indoor air quality performance

EQp1 | Required

Intent

To establish minimum indoor air quality (IAQ) performance to enhance indoor air quality in buildings, thus contributing to the comfort and well-being of the occupants.

Requirements

Meet the minimum requirements of Sections 4 through 7 of ASHRAE 62.1–2007, Ventilation for Acceptable Indoor Air Quality (with errata but without addenda1). Projects outside the U.S. may use a local equivalent to ASHRAE Standard 62.1-2007 for breathing zone minimum ventilation rates.

AND

Case 1. Mechanically ventilated spaces
Option 1. ASHRAE standard 62.1-2007 or non-U.S. equivalent

Modify or maintain the existing outside air ventilation distribution system to supply at least the outdoor air ventilation rate required by ASHRAE 62.1–2007 (with errata but without addenda1). Projects outside the U.S. may use a local equivalent to ASHRAE Standard 62.1-2007 for breathing zone minimum ventilation rates.

OR

Option 2. CEN standard EN 15251: 2007

Projects outside the U.S. may modify or maintain each outside air intake, supply air fan and/or ventilation distribution system to supply at least the outdoor air ventilation rate required by Annex B of Comité Européen de Normalisation (CEN) Standard EN 15251: 2007, Indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality, thermal environment, lighting and acoustics.

If the project team cannot meet the outside air requirements of the above standards, document the space and system constraints that make it not possible, complete an engineering assessment of the system’s maximum cubic feet per minute (cfm) capability toward meeting the requirements of the above standards, and achieve those levels, with a minimum of 10 cfm (0.28 cubic meters per minute) per person. All other requirements must be met.

OR

Case 2. Naturally ventilated spaces

Naturally ventilated buildings must comply with ASHRAE Standard 62.1-2007, Paragraph 5.1 (with errata but without addenda1).

Modify or maintain the existing outside air ventilation distribution system to supply at least the outdoor air ventilation rate required by ASHRAE Standard 62.1–2007 (with errata but without addenda1). If the project team cannot meet the outside air requirements of ASHRAE 62.1–2007 (with errata but without addenda1), document the space and system constraints that make it not possible, complete an engineering assessment of the system’s maximum cubic feet per minute (cfm) capability toward meeting the requirements of ASHRAE 62.1– 2007 (with errata but without addenda1), and achieve those levels, with a minimum of 10 cfm (0.28 cubic meters per minute) per person. All other requirements must be met.

Join LEEDuser

Ask questions, share tips, and get notified of new forum posts by joining LEEDuser, a tool developed by BuildingGreen and supported by USGBC!

  • Share on Twitter
  • Share on Facebook
  • Share on LinkedIn
  • Print to PDF
Sample forms

No sample form available for this credit.

View all sample forms

0 commentsLeave a comment

Leave a comment Don't have an account? Create one

You must be signed in to leave a comment.