Water Use Reduction Additional Guidance
| ID | WEp1AG |
|---|---|
| Format | |
| Type | Guidance |
| Shared by | Batya Metalitz |
| Published on | 1 Dec 2009 |
| Effective on | 1 Apr 2013 |
Provides guidance for fixture groups, total daily uses calculation, dual flush toilet flow rates, public metering faucet flow rate conversion, non-potable water use alternative compliance path and gender ratio guidance.
WEp1: Water Use Reduction Additional Guidance, version 8, Updated 4/1/2013
The guidance has been updated to clarify that the blow-out fixture guidance is only available to rating systems that include blow-out fixtures in the prerequisite requirements (not EBOM), and to include the 0.25 gpc baseline for the metering type / autocontrol lavatory faucet in footnote 2 of Table 1 Non-residential Default Fixture Uses to align with the 4/1/2013 Addendum which clarified that the autocontrol lavatory faucet baseline is 0.25 gpc for the baseline case.