| Credit Name | EQp2 - Environmental Tobacco Smoke (ETS) control |
|---|---|
| Credit Category | Indoor environmental quality |
| International Applicable | Yes |
| Campus Applicable | No |
Rating System
LEED BD+C: New Construction, LEED BD+C: Core and Shell, LEED BD+C: Hospitality, LEED ID+C: Retail, LEED O+M: Existing Buildings
Rating System Version
v3 - LEED 2009
Inquiry
Our project consists of a new hotel in its entirety. It is a stand-alone building with its own separate entrance, restrooms, lobby, and amenities. The owner is considering connecting the hotel to an existing casino, where smoking is allowed. The Supplemental Guidance to the LEED MPR specifically mentions casinos and EQp2, and indicates there will be no exceptions to this MPR to allow for partial building certification. We do not believe this applies to us since we are building a new stand-alone hotel in its entirety, not a partial building. EQp2 indicates that if there is a smoking room within a LEED building, it shall be operated under an average negative pressure of 5 Pa, etc. We are seeking clarification on whether or not it is acceptable to connect our new hotel to an existing building with smoking, and if yes, what rules need to be followed regarding the connection. If a connection to a smoking building is allowed, we would prohibit smoking in the existing building within 25 feet of the new hotel building entrance. If a connection to a smoking building is allowed, can it have an open area, in which we maintain a high air velocity to eliminate smoke migration between the two buildings? Or does it require doors between the two buildings and maintenance of 5 Pa of pressure similar to a smoking room?