Created on LEED Interpretation

ID#

li-1574

Credit NameEAc1 - Optimize energy performance
Credit CategoryEnergy & atmosphere
International ApplicableYes

Rating System

LEED BD+C: New Construction

Rating System Version

v2 - LEED 2.2

Inquiry

Exception c from G3.1.1 of ASHRAE 90.1-2004 indicates we should use separate single zone systems conforming with the requirements of System 3 or System 4 in our baseline energy model for any zones having special pressurization requirements. We assume this would include various laboratory and hospital spaces, among others. Can these baseline systems be modeled as constant volume reheat systems? In a humid climate, Systems 3 and 4 would not be suitable for a laboratory with 100% or high outside air percentages unless reheat was allowed. Exception c to section 6.5.2.1 allows simultaneous heating and cooling where there are special pressurization relationships, but the Performance Rating Method of ASHRAE 90.1-2004 does not seem to reference using prescriptive requirements to determine how our baseline model can be set up.