Our project is a multiple building high-end condominium-resort project. This question relates to the requirements of lighting as it pertains to ASHRAE/IESNA 90.1-2004. In ASHRAE 90.1-2004, section 9.1.1, exceptions (b) lists that this section does not apply to lighting within living units. However table 9.5.1 Lighting Power Densities Using the Building Area Method lists "Multi-family" building area type with a 0.7 W/SF. Please clarify for the purposes of EAp2 and EA credit 1, the applicable interpretation of the Standard. Does the entire building have to meet the 0.7W/SF requirement as an average?