Created on LEED Interpretation

ID#

li-1840

Credit NameEQc1 - Outdoor air delivery monitoring
Credit CategoryIndoor environmental quality
International ApplicableYes
Campus ApplicableNo

Rating System

LEED BD+C: New Construction, LEED O+M: Existing Buildings, LEED ID+C: Commercial Interiors, LEED BD+C: Core and Shell, LEED BD+C: Schools

Rating System Version

v3 - LEED 2009, v3 - LEED 2008, v2 - Schools 2007, v2 - LEED 2.2, v2 - LEED 2.0

Inquiry

To monitor outside air intake we propose to utilize the DDC controls to measure temperatures for the outside air, return air, mixed air, and supply air. The DDC calculations will result in the total CFM of outside air delivered well within the 15% accuracy required. Additionally, the controls configuration will provide alarms whenever the delivered amount of outside air is below the minimum threshold. As a secondary measure, CO2 sensors will be required for ALL building tenants per the LEED CI credit EQ 1. This project exceeds the minimum ventilation requirements of ASHRAE Standard 62.1-2004 by well over 30%. These three parameters will ensure that the minimum outside air will be delivered, monitored, and alarmed per the requirements of LEED CS EQ credit 1. Will our proposal meet the intent of this credit?