ID#
li-1876
| Credit Name | EAc1 - Optimize energy performance |
|---|---|
| Credit Category | Energy & atmosphere |
| International Applicable | Yes |
| Campus Applicable | No |
Rating System
LEED BD+C: New Construction
Rating System Version
v2 - LEED 2.2, v2 - LEED 2.1, v2 - LEED 2.0
Inquiry
Our project team requests clarification of the applicability of ASHRAE 90.1-1999 section 9.3.1.2 Additional Interior Lighting Power (b) in determining the baseline space by space lighting power densities. In determining energy code compliance, the referenced section allows the values in Table 9.3.1.2 to be increased by up to 0.35 W/ft2 for those spaces where visual display terminals are the primary viewing task and fixtures are installed that meet the detailed luminance at angle criteria. Please confirm that for any space type where visual display terminals are the primary viewing task and the proposed fixtures meet the detailed luminance at angle criteria, the baseline lighting power density shall be the value from Table 9.3.1.2 plus an additional allowance of 0.35 W/ft2 from 9.3.1.2 Additional Interior Lighting Power (b), regardless of the proposed lighting power density.