ID#
li-1915
| Credit Name | EAc1 - Optimize energy performance |
|---|---|
| Credit Category | Energy & atmosphere |
| International Applicable | Yes |
Rating System
LEED BD+C: New Construction, LEED BD+C: New Construction, LEED BD+C: Schools, LEED BD+C: Schools, LEED BD+C: Core and Shell
Rating System Version
v2 - LEED 2.2, v3 - LEED 2009, v2 - Schools 2007, v3 - LEED 2009, v3 - LEED 2009
Inquiry
The purpose of this CIR is to obtain confirmation of what is considered New Buildings vs. Existing Building Renovations within Option 1 of this credit. The project consists of a 120,000 SF existing building, which is part of and connected to other buildings in a corporate campus. The building was recently used for offices, which is the predominate use of the campus. There is no central mechanical plant for the campus-each building has its own mechanical system. The building is being converted to a large data center. The building\'s exterior shell will be retained but the existing mechanical and electrical systems, as well as all interior partitions, ceilings and finishes, will be removed. In short, the building is being gutted. We will be submitting this credit under Option 1: Whole Building Energy Simulation. The mechanical engineer is confident that the building will save at least 7% energy costs but not sure it will achieve 14%. Since we are required to achieve 2 points in this credit to achieve certification, we wish to be certain that the project will be considered Existing Building Renovation for the purpose of awarding points for energy savings.