Created on LEED Interpretation

ID#

li-2297

Credit NameEAc2 - On-site renewable energy
Credit CategoryEnergy & atmosphere
International ApplicableYes
Campus ApplicableNo

Rating System

LEED BD+C: New Construction, LEED O+M: Existing Buildings, LEED BD+C: Core and Shell, LEED BD+C: Schools

Rating System Version

v3 - LEED 2009, v2 - Schools 2007, v2 - LEED 2.2

Inquiry

Our community college campus includes an existing 1.06mW solar field that backfeeds two existing metered services. Additional metered services on the campus are serviced by the utility company campus \'loop\', but are not fed directly by the solar array. The solar array currently accounts for 25% of power provided to the existing campus (documentation available). Two new buildings are under construction on campus. Building A is a new 60,000 s.f., 3-story Office and Administration building, which is fed by one of the two metered electrical services tied directly to the solar array. Building B is a 77,000 s.f., two-story Fine Arts facility, which will require a new metered service from the utility company campus \'loop\', but are not fed directly by the solar array. A CIR Ruling dated 08/13/2007 implies that an existing PV array may be applied to new construction on a campus, therefore we would like to pursue EA credit #2 for both projects. Our intent is to provide documentation to express the anticipated annual energy use of each new building as a percentage of the overall energy use on campus, and to apply the same percentage of the power generated by the solar array towards this credit.

Logging out the application..