ID#
li-2339
| Credit Name | EAc1 - Optimize energy performance |
|---|---|
| Credit Category | Energy & atmosphere |
| International Applicable | Yes |
Rating System
LEED BD+C: New Construction, LEED BD+C: New Construction, LEED BD+C: Schools, LEED BD+C: Schools, LEED ID+C: Commercial Interiors, LEED BD+C: Core and Shell, LEED O+M: Existing Buildings
Rating System Version
v2 - LEED 2.2, v3 - LEED 2009, v2 - Schools 2007, v3 - LEED 2009, v3 - LEED 2009, v3 - LEED 2009, v3 - LEED 2009
Inquiry
Our project is a 65,000 SF injection molding manufacturing facility and office near Detroit, MI. The project consists of 10,000 SF of air-conditioned office space, and 55,000 SF of air-conditioned manufacturing space, which includes injection molding equipment, as well as occupied assembly areas. The energy required for the manufacturing process exceeds 85% of the facility\'s total energy load. To achieve the 14% minimum energy savings, process load energy savings must be taken into account. As a result of the high energy loads associated with the manufacturing process, as well as the energy not falling under ASHRAE 90.1-2004, an exceptional calculation method must be established for the manufacturing area. Both the office area and the manufacturing area are conditioned. Space cooling in these areas will be achieved through constant volume rooftop units, and will be modeled through a standard energy modeling software like Trane Trace 700. The manufacturing process includes injection molding machinery which is cooled through a chiller & cooling tower assembly. The load on the chiller and cooling tower will not fluctuate (except for operational and non-operational hours, which will be achieved through a schedule). The chiller and cooling tower performance will be run in a separate energy model using this constant load to determine the overall energy used based on the outdoor air conditions throughout the year. The Chiller and cooling tower energy used will then be input into the original model as annual process energy. The Chiller and Cooling Tower efficiencies for the baseline will be based off ASHRAE 90.1-2004 minimum standards. The injection molding equipment proposed is state-of-the-art and very energy efficient compared to the standard injection molding machinery that is the industry standard. Using the client-provided operational times for the equipment we will be able to estimate the total energy used by this injection molding equipment, as well as the total energy that would be used by industry standard equipment. This will be used to determine the annual energy for both the baseline and the proposed design. We will then input these amounts into the original energy model as annual process energy. For comparison purposes, we also have a similar plant by the same client that uses the industry standard machines. By comparing the amount of equipment and square footage of this plant, we can achieve a very accurate idea of how much energy the new plant is saving. All calculations showing how the machinery energy was determined, and results of planned field monitoring, will be explained in an excel spreadsheet. Equipment descriptions and energy loads will be shown for all machines that will be used, as well as for comparable industry standard machines. Once the process equipment, both baseline and proposed, have been input into the overall energy model as process loads, the standard reports issued from the model will be used for the LEED Reports. In addition, we will provide the sub-energy models of the process equipment that is weather-based. Please confirm that our assumptions and method of calculating the process energy load for both the base and proposed design cases are acceptable for EAc1.