Accessibility Tools

  • Increase text
  • Decrease text
  • High contrast
  • Negative contrast
  • Add grayscale
  • Remove grayscale
  • Add lightbackground
  • Remove lightbackground
  • Reset
Created on LEED Interpretation

ID#

li-2531

Credit NameEAp2 - Minimum energy efficiency performance
Credit CategoryEnergy & atmosphere
International ApplicableYes
Campus ApplicableNo

Rating System

LEED O+M: Existing Buildings

Rating System Version

v3 - LEED 2009, v3 - LEED 2008

Inquiry

We are planning to submit our office building for LEED O&M certification. Our 148,331 square foot building has a 531 square foot computer data center. The data center has a high energy use intensity, using approximately 154 watts per square foot, based on sub metering data collected over the last 12 months. The Energy Star Portfolio Manager program does not adequately account for the data center power use. Excluding the data center significantly reduces our Energy Star score across the building since the data center power density is not accurately represented by Portfolio Manager. The data center has a dedicated sub-meter to accurately capture and monitor the energy used. We would like to pull the data center out of the Energy Star Portfolio Manager scoring system. Energy Star will allow us to pull out the square footage of the data center and the total energy used by the data center for Energy Star Certification if we have 12 months of actual metering data and the data center area accounts for less than 10% of the total area. This facility meets both criteria. Please confirm that this approach to demonstrating compliance with LEED O&M EA Prerequisite 2 and Credit 1 is acceptable to USGBC.

Logging out the application..