ID#
li-5089
| Credit Name | EAc5 - Measurement and verification |
|---|---|
| Credit Category | Energy & atmosphere |
| International Applicable | Yes |
Rating System
LEED BD+C: New Construction, LEED BD+C: New Construction, LEED BD+C: Core and Shell
Rating System Version
v2 - LEED 2.2, v3 - LEED 2009, v3 - LEED 2009
Inquiry
To meet the requires of LEED-NC Version 2.2, EA Credit 5, are there any end uses that require continuously metering when IPMVP Option D is used? Specifically the end uses required under LEED-NC Version 2.1 were: 1. Lighting systems and controls 2. Constant and variable load motors 3. Variable frequency drive (VFD) operation 4. Chiller efficiency at variable loads (kW/ton) 5. Cooling load 6. Air and water economizer and heat recovery cycles 7. Air distribution static pressure and ventilation air volumes 8. Boiler efficiencies 9. Building-related process energy systems and equipment 10.Indoor water risers and outdoor irrigation systems Or, can these end uses be captured as an aggregate at the utility meter?