Created on LEED Interpretation

ID#

li-5146

Credit NameEQc7 - Thermal comfort - design
Credit CategoryIndoor environmental quality
International ApplicableYes

Rating System

LEED BD+C: Schools, LEED BD+C: Core and Shell, LEED BD+C: Core and Shell

Rating System Version

v2 - Schools 2007, v2 - LEED 2.0, v3 - LEED 2009

Inquiry

EQc10 requires compliance with EQc7.1 "Thermal Comfort, Design". ASHRAE 55 uses absolute humidity as the upper moisture limit. EQc10 requires a 60% RH which cuts the ASHRAE 55 absolute humidity in half, or more depending on how cold it gets inside a room when the systems are turned off. If natural ventilation is used at all, and any windows are left partially opened at night, there would be no way to control the humidity to a 60% RH. It is problematic to maintaining a humidity level below 60% when the spaces are unoccupied. The only way to pull humidity out of the space is to run the air conditioning equipment to create condensation, which is itself a potential moisture problem, or to run conditioning systems in heating mode, and so in order to achieve the required humidity levels during unoccupied periods is to potentially run the air conditioning equipment 24 hours a day, seven days a week controlled by a humidistat in the space. There is an apparent flaw in this LEEDS for Schools credit as to comply with this credit the District would need to use up energy and pay higher utility bills during long periods, such as the summer, when the campus is not in use. The USGBC is targeting reducing the carbon footprint of buildings, and the 60% relative humidity requirement is inconsistent with that objective. We suggest some possible alternative mold control techniques during construction of the building instead of conditioning for 60% relative humidity such as: 1. Install mold resistant gypsum board 2. Install weather barrier under exterior finish materials and slab on grade 3. Capillary breaks for footings 4. Provide special inspection for openings and penetrations in the building envelope

Logging out the application..