Created on LEED Interpretation

ID#

li-5192

Credit NameSSc8 - Light pollution reduction
Credit CategorySustainable sites
International ApplicableYes

Rating System

LEED BD+C: New Construction, LEED BD+C: New Construction, LEED BD+C: Schools, LEED BD+C: Schools, LEED BD+C: Core and Shell

Rating System Version

v2 - LEED 2.2, v3 - LEED 2009, v2 - Schools 2007, v3 - LEED 2009, v3 - LEED 2009

Inquiry

Our project is an office building located in an area surrounded mostly by residential properties. The office building and site will comply with the Light Pollution Reduction credit. The firm that will occupy this office building works on many projects of a sensitive nature so security is a significant concern, both for employees arriving early or working after dark and for protection of the facility from intrusion. Is it acceptable to include motion-sensor activated lights that do not fall within the allowable site lighting wattage? These lights would be located in the immediate vicinity of the building and would only be enabled to turn on when other site lights are off. They would only remain on for a limited time following activation. If such motion-sensor activated lights are allowed, can they be excluded from the other requirements of this credit, property line illuminance and uplight components, since their purpose is only safety and security?